51
Battery Parameters
This page provides the battery status and battery run-time information. This page will
refresh automatically at a user-defined rate. To change or view the refresh rate setting,
select RemotEye II Management - HTTP Page Refresh Rates.
Battery Status
This field shows the status of the UPS batteries. These readings include: Unknown,
Normal, Low, Depleted, Discharging, and Failure.
Elapsed Time On Battery Power
This field shows the elapsed time (in seconds) since the UPS switched to battery
power.
Battery Capacity Remaining (option)
This field shows the remaining battery capacity expressed as a percentage of full
capacity.
Battery Estimated Minutes Remaining (option)
This field shows the remaining minutes of the UPS to sustain the current load.
Battery Voltage
This field shows the battery voltage in VDC.
Battery Voltage Percent
This field shows the battery voltage in %.
Battery Current (option)
This field shows the present battery current in %.
Battery Temperature (option)
This field shows the internal UPS temperature expressed in
o
C.
Battery Last Replaced Date
This field shows the last replacement date of the UPS system's batteries. This value is
displayed in the dd/mm/yyyy format. When the UPS batteries are replaced, this value
should be adjusted accordingly by the service center.
Battery Life Remaining
This field shows the remaining battery life. The maximum battery lifetime is 5 years.
This shows the remaining battery lifetime in months.
Battery Rated Backup Time
This field allows the administrator to configure the estimated battery backup time (in
minutes) during power failure at 100% load. The default is 0 minutes.