– 16 –
Group control for system of multiple units
One remote controller can control maximum 8 indoor units as a group.
▼
Group control in single system
• For wiring procedure and wiring method of the individual line (Identical refrigerant line) system, follow to
“Electrical connection”.
• Wiring between lines is performed in the following procedure.
Connect the terminal block (A/B) of the indoor unit connected with a remote controller to the terminal blocks (A/
B) of the indoor units of other indoor units by wiring the inter-unit wire of the remote controller.
• When the power supply has been turned on, the automatic address setup starts and which indicates that address
is being set up flashes on the display part in about 3 minutes. During setup of automatic address, the remote
controller operation is not accepted.
Required time up to the finish of automatic addressing is approx. 5 minutes.
NOTE
In some cases, it is necessary to change the address manually after setup of the automatic address according to the
system configuration of the group control.
• The follow mentioned system configuration is a case when complex systems in which systems of the simultaneous
twin and simultaneous triple unit is controlled as a group by a remote controller.
(Example) Group control for complex system
The above address is set by the automatic addressing when the power is turned on. However, line
addresses and indoor addresses are set randomly. For this reason, change the setting to match line
addresses with indoor addresses.
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Remote controller
Finish of address setup by power-ON
(Max. 8 units)
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Line system
Indoor No.
After setup of
automatic
address
(Example of random
setup)
After setup
change of
manual address
(Example of address setup change)
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Line address
Group address
Indoor address
Address: 1-1-1
Address: 2-1-2
Address: 2-2-2
Address: 1-1-2
Address: 2-1-2
Address: 3-3-1
Procedure
example 1
<Single system> <Twin system>
<Triple system>
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Remote controller
Address: 3-1-2
Address: 3-2-2
Address: 3-3-2
Address: 3-1-2
Address: 2-2-2
Address: 1-2-2
[Procedure example]
Manual address setup procedure
While the operation stops, change the setup.
(Stop the operation of the unit.)
1
Push
+
+
buttons simultaneously
for 4 seconds or more. After a while, the
display part flashes as shown below. Check
the displayed CODE No. is [10].
• When the CODE No. is other than [
10
], push
button to erase the display and repeat
procedure from the first step.
(After pushing
button, operation of the
remote controller is not accepted for
approx. 1 minute.)
(For a group control, No. of the firstly displayed
indoor unit becomes the header unit.)
2
Every time
button is pushed, the
indoor UNIT No. in the group control is
displayed in order. Select the indoor unit of
which setup is changed.
In this time, the position of the indoor unit of which
setup is changed can be confirmed because fan of
the selected indoor unit operate.
3
1. Specify CODE No. [
12
] with TEMP.
/
buttons.
(CODE No. [
12
]: Line address)
2. Change the line address from [
3
] to [
2
] with TIME
/
buttons.
3. Push
button.
In this time, the setup finishes when the display
changes from flashing to lighting.
4
1. Specify CODE No. [
13
] with TEMP.
/
buttons.
(CODE No. [
13
]: Indoor address)
2. Change the indoor address from [
3
] to [
2
] TIME
/
buttons.
3. Push
button.
In this time, the setup finishes when the display
changes from flashing to lighting.
2,6
1
7
3
-1,
4
5
6
-1,
-1,
7
3
-3,
4
-3,
3
-2,
4
-2,
5
-2
5
-3,
(* Display changes according to
the model No. of indoor unit.)
Indoor UNIT No. before setup change is displayed.
Indoor UNIT No. before setup change is displayed.
31-EN
32-EN
Summary of Contents for RAV-SM404MUT-E
Page 24: ...EH99885797 ...
Page 48: ...EH99885797 ...
Page 72: ...EH99885797 ...
Page 96: ...EH99885797 ...
Page 120: ...EH99885797 ...
Page 144: ...EH99885797 ...
Page 168: ...EH99885797 ...
Page 192: ...EH99885797 ...
Page 216: ...EH99885797 ...
Page 240: ...EH99885797 ...
Page 264: ...EH99885797 ...
Page 288: ...EH99885797 ...