– 12 –
Wiring between indoor unit and outdoor unit
1. Figure below shows the wiring connections between the indoor and outdoor units and between the indoor units
and remote controller. The wires indicated by the broken lines or dot-and-dash lines are provided at the locally.
2. Refer to the both indoor and outdoor unit wiring diagrams.
3. The power of the indoor unit is supplied from the outdoor unit.
Wiring diagram
* Use 2-core shield wire (MVVS 0.5 to 2.0 mm
2
or more) for the remote controller wiring in the simultaneous twin,
simultaneous triple and simultaneous double twin systems to prevent noise problems. Connect both ends of the
shield wire to earth leads.
* Connect earth wires for each indoor unit in the simultaneous twin, simultaneous triple and simultaneous double
twin systems.
Single system
Simultaneous twin system
Simultaneous triple and double twin system
A B
1
1
2
2
3
3
Outdoor side
Power supply
Remote controller
Remote controller wiring
Indoor side
Indoor / Outdoor
connecting wires
A B
1
2
3
A B
1
1
2
2
3
3
Power supply
Remote controller
inter-unit wiring
Indoor
side
Indoor power
inter-unit wiring
Outdoor side
Remote controller
Remote controller wiring
Indoor side
Indoor / Outdoor connecting
wires
A B
1
2
3
A B
1
2
3
A B
1
2
3
A B
1
2
3
1
2
3
Power supply
Remote controller
inter-unit wiring
Indoor side
Indoor power
inter-unit wiring
Remote controller
inter-unit wiring
Indoor side
Remote controller
inter-unit wiring
Indoor side
Triple
Double twin
Indoor power
inter-unit wiring
Indoor power
inter-unit wiring
Outdoor side
Remote controller
Remote controller
wiring
Indoor side
Indoor / Outdoor
connecting wires
Wire connection
REQUIREMENT
• Connect the wires matching the terminal numbers. Incorrect connection causes a trouble.
• Pass the wires through the bushing of wire connection holes of the indoor unit.
• Keep a margin (Approx. 100 mm) on a wire to hang down the electrical control box at servicing or other purpose.
• The low-voltage circuit is provided for the remote controller. (Do not connect the high-voltage circuit)
• Remove the cover of the electrical control box by taking off the mounting screws (3 positions) and pushing the
hooking section. (The cover of the electrical control box remains hanged to the hinge.)
• Connect the indoor / outdoor connecting wires and remote controller wire to the terminal block of the electrical
control box. (Do not apply tension to the connecting section of the terminal block.)
• Tighten the screws of the terminal block, and fix the wires with cord clamp attached to the electrical control box.
(Do not apply tension to the connecting section of the terminal block.)
• Using the attached heat insulator material, seal the pipe connecting port. Otherwise, dewing may be caused.
• Mount the cover of the electrical control box without pinching wires. (Mount the cover after wiring on the ceiling
panel.)
A B
2
1
3
1
2
3
A
B
Screws
Cord clamp
Adhered surface
Remote controller
terminal block
Notched section
P.C. board
Screw
Electrical control
box
Cover of electrical control box
Indoor / Outdoor
connecting terminal
block
Heat insulator B
Heat insulation to wiring connecting port
Heat
insulator A
Hooking section
23-EN
24-EN
Summary of Contents for RAV-SM404MUT-E
Page 24: ...EH99885797 ...
Page 48: ...EH99885797 ...
Page 72: ...EH99885797 ...
Page 96: ...EH99885797 ...
Page 120: ...EH99885797 ...
Page 144: ...EH99885797 ...
Page 168: ...EH99885797 ...
Page 192: ...EH99885797 ...
Page 216: ...EH99885797 ...
Page 240: ...EH99885797 ...
Page 264: ...EH99885797 ...
Page 288: ...EH99885797 ...