Refrigerant piping

‡

Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the compressor 
is operated with the valve open and without refrigerant pipe, the compressor sucks air and the refrigeration cycles is 
over pressurized, which may cause a injury.

‡

Tighten the flare nut with a torque wrench in the specified manner. Excessive tighten of the flare nut may cause a 
crack in the flare nut after a long period, which may result in refrigerant leakage.

‡

When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and purge 
the air completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle. Failure to purge 
the air completely may cause the air conditioner to malfunction.

‡

Nitrogen gas must be used for the airtight test.

‡

The charge hose must be connected in such a way that it is not slack.

Electrical wiring

‡

Only a qualified installer(*1) or qualified service person(*1) is allowed to carry out the electrical work of the air 
conditioner. Under no circumstances must this work be done by an unqualified individual since failure to carry out the 
work properly may result in electric shocks and/or electrical leaks.

‡

The appliance shall be installed in accordance with national wiring regulations. Capacity shortages of the power 
circuit or an incomplete installation may cause an electric shock or fire.

‡

Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations and 
laws. Use of wiring which does not meet the specifications may give rise to electric shocks, electrical leakage, 
smoking and/or a fire.

‡

Be sure to connect earth wire. (Grounding work) 
Incomplete grounding causes an electric shock.

‡

Do not connect ground wires to gas pipes, water pipes, and lightning rods or ground wires for telephone wires.

‡

After completing the repair or relocation work, check that the ground wires are connected properly.

‡

Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local 
regulations and laws.

‡

Install the circuit breaker where it can be easily accessed by the agent.

‡

When installing the circuit breaker outdoors, install one which is designed to be used outdoors.

‡

Under no circumstances must the power cable be extended. Connection trouble in the places where the cable is 
extended may give rise to smoking and/or a fire.

Test run

‡

Before operating the air conditioner after having completed the work, check that the electrical control box cover of the 
indoor unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position. You may 
receive an electric shock etc. if the power is turned on without first conducting these checks.

‡

When you have noticed that some kind of trouble (such as when an error display has appeared, there is a smell of 
burning, abnormal sounds are heard, the air conditioner fails to cool or heat or water is leaking) has occurred in the 
air conditioner, do not touch the air conditioner yourself but set the circuit breaker to the OFF position, and contact a 
qualified service person. Take steps to ensure that the power will not be turned on (by marking “out of service” near 
the circuit breaker, for instance) until qualified service person arrives. Continuing to use the air conditioner in the 
trouble status may cause mechanical problems to escalate or result in electric shocks, etc.

‡

After the work has finished, be sure to use an insulation tester set (500 V Megger) to check the resistance is 1 M  
or more between the charge section and the non-charge metal section (Earth section). If the resistance value is low, 
a disaster such as a leak or electric shock is caused at user’s side.

‡

Upon completion of the installation work, check for refrigerant leaks and check the insulation resistance and water 
drainage. Then conduct a test run to check that the air conditioner is operating properly.

‡

After the installation work, confirm that refrigerant gas does not leak. If refrigerant gas leaks into the room and flows 
near a fire source, such as a cooking range, noxious gas may be generated.

Explanations given to user

‡

Upon completion of the installation work, tell the user where the circuit breaker is located. If the user does not know 
where the circuit breaker is, he or she will not be able to turn it off in the event that trouble has occurred in the air 
conditioner.

‡

If you have discovered that the fan guard is damaged, do not approach the outdoor unit but set the circuit breaker to 
the OFF position, and contact a qualified service person(*1) to have the repairs done. Do not set the circuit breaker 
to the ON position until the repairs are completed.

‡

After the installation work, follow the Owner’s Manual to explain to the customer how to use and maintain the unit.

Relocation

‡

Only a qualified installer(*1) or qualified service person(*1) is allowed to relocate the air conditioner. It is dangerous 
for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, 
noise and/or vibration may result.

‡

When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. 
Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air, 
etc. to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly 
resulting in reputing, injury, etc.

(*1) Refer to the “Definition of Qualified Installer or Qualified Service Person.”

CAUTION

New refrigerant air conditioner installation

‡

This air conditioner adopts the new HFC refrigerant (R410A) which does not destroy ozone layer.

R410A refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because the working 
pressure of R410A refrigerant is approx. 1.6 times as that of refrigerant R22. Accompanied with the adoption of the new 
refrigerant, the refrigeration machine oil has also been changed. Therefore, during installation work, be sure that water, 
dust, former refrigerant, or refrigeration machine oil does not enter the new type refrigerant R410A air conditioner circuit.
To prevent mixing of refrigerant or refrigerating machine oil, the sizes of connecting sections of charging port on main 
unit and installation tools are different from those of the conventional refrigerant units. Accordingly, special tools are 
required for the new refrigerant (R410A) units. For connecting pipes, use new and clean piping materials with high 
pressure fittings made for R410A only, so that water and/or dust does not enter.

To disconnect the appliance from main power supply

‡

This appliance must be connected to the main power supply by means of a switch with a contact separation of at 
least 3 mm.

‡

The installation fuse (all fuse types can be used) must be used for the power supply line of this conditioner.

Do not wash air conditioners with pressure washers

‡

Electric leaks may cause electric shocks or fires.

EN

ID

1115250101_EN.indd   4

1115250101_EN.indd   4

8/24/13   9:20 AM

8/24/13   9:20 AM

Summary of Contents for RAV-SM1104ATJP-E

Page 1: ...Installation Manual Outdoor Unit Model name RAV SM1104ATP E RAV SM1104ATJP E RAV SM1404ATP E RAV SM1404ATJP E For commercial use English 1115250101 1115250101_cover indd C1 1115250101_cover indd C1 8 24 13 9 22 AM 8 24 13 9 22 AM ...

Page 2: ...r equal to Ssc 1 Ssc 1 Ssc KVA Model Single system Twin system RAV SM1104AT J P E 740 880 RAV SM1404AT J P E 740 880 Contents 1 Precautions for safety 3 2 Accessory parts 29 3 Installation of new refrigerant air conditioner 29 4 Installation conditions 30 5 Refrigerant piping 33 6 Air purging 35 7 Electrical work 36 8 Earthing 37 9 Finishing 37 1 Précautions relatives à la sécurité 6 1 Sicherheits...

Page 3: ...his work Qualified service person The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporation He or she has been trained to install repair maintain relocate and remove the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such operations by an individual o...

Page 4: ...hing during installation servicing and removal Do not touch the aluminum fin of the outdoor unit You may injure yourself if you do so If the fin must be touched for some reason first put on protective gloves and safety work clothing and then proceed Do not climb onto or place objects on top of the outdoor unit You may fall or the objects may fall off of the outdoor unit and result in injury When w...

Page 5: ... in electric shocks etc After the work has finished be sure to use an insulation tester set 500 V Megger to check the resistance is 1 M or more between the charge section and the non charge metal section Earth section If the resistance value is low a disaster such as a leak or electric shock is caused at user s side Upon completion of the installation work check for refrigerant leaks and check the...

Page 6: ...e est une personne qui installe répare entretient déplace et enlève les climatiseurs fabriqués par Toshiba Carrier Corporation Il ou elle a été formé pour installer réparer entretenir déplacer et enlever les climatiseurs fabriqués par Toshiba Carrier Corporation ou alternativement il ou elle a reçu des consignes pour de telles opérations par une ou des personnes qui ont été formées et a par conséq...

Page 7: ...Travail en cours à proximité du disjoncteur pendant l installation l entretien la réparation ou la dépose Un danger d électrocution est possible si le disjoncteur est réglé sur ON par erreur Seul un installateur qualifié 1 ou une personne d entretien qualifiée 1 est autorisé à entreprendre un travail en hauteur à l aide d un pied de 50 cm minimum Portez des gants de protection ainsi que des vêteme...

Page 8: ...au est présente est survenu au niveau du climatiseur ne touchez pas le climatiseur vous même et réglez le disjoncteur sur la position OFF ensuite contactez une personne d entretien qualifiée Prenez des mesures pour garantir que l alimentation ne sera pas branchée en indiquant hors service près du disjoncteur par exemple jusqu à ce que le technicien d entretien qualifié arrive Continuer à utiliser ...

Page 9: ...nstruiert worden sein und ist somit mit dem für diese Arbeiten erforderlichen Wissen bestens vertraut Qualifizierter Servicetechniker Der qualifizierte Servicetechniker ist ein Auftragnehmer der die von der Toshiba Carrier Corporation hergestellten Klimaanlagen installiert repariert wartet umsetzt und entsorgt Dieser Auftragnehmer wurde speziell geschult die von der Toshiba Carrier Corporation her...

Page 10: ... nicht einschalten neben dem Schutzschalter an während die Installations Wartungs Reparatur oder Ausbauarbeiten ausgeführt werden Es besteht die Gefahr von Stromschlägen wenn der Schutzschalter fälschlicherweise auf ON ein gestellt wird Nur ein qualifizierter Installateur 1 oder ein qualifizierter Servicetechniker 1 darf Arbeiten in der Höhe unter Verwendung von Trittstufen Leitern usw mit einer H...

Page 11: ...elbst an der Klimaanlage sondern stellen Sie den Schutzschalter auf die Position OFF aus und wenden Sie sich an einen Servicetechniker Stellen Sie sicher dass der Strom nicht wieder eingeschaltet wird indem Sie beispielsweise den Schutzschalter durch außer Betrieb kennzeichnen bis ein qualifizierter Servicetechniker eintrifft Die weitere Verwendung der Klimaanlage in diesem fehlerhaften Zustand ka...

Page 12: ... dell assistenza qualificato Il tecnico dell assistenza qualificato è una persona che installa ripara sottopone a manutenzione trasferisce e rimuove i condizionatori d aria prodotti da Toshiba Carrier Corporation Tale persona è stata addestrata a installare riparare sottoporre a manutenzione trasferire e rimuovere i condizionatori d aria prodotti da Toshiba Carrier Corporation o in alternativa ha ...

Page 13: ...e Lavori in corso in prossimità dell interruttore automatico durante l esecuzione di lavori di installazione manutenzione riparazione o rimozione Qualora l interruttore automatico sia impostato su ON acceso per errore sussiste il pericolo di scosse elettriche Solo un installatore qualificato 1 o un tecnico dell assistenza qualificato 1 sono autorizzati a eseguire lavori in altezza utilizzando un s...

Page 14: ...tare l interruttore automatico sulla posizione OFF spento e contattare un tecnico dell assistenza qualificato Adottare delle misure per assicurare che l unità non venga accesa ad esempio scrivendo fuori servizio in prossimità dell interruttore automatico fino all arrivo di un tecnico dell assistenza qualificato Qualora si continui a utilizzare il condizionatore d aria in presenza di un problema si...

Page 15: ...ficada La persona de mantenimiento cualificada es una persona que instala repara mantiene recoloca y se deshace de los aparatos de aire acondicionado fabricados por Toshiba Carrier Corporation Él o ella han sido formados para instalar reparar mantener recolocar y deshacerse de los aparatos de aire acondicionado fabricados por Toshiba Carrier Corporation o en otro caso han recibido instrucciones pa...

Page 16: ...e 50 cm o más Utilice guantes de protección y ropa de trabajo segura durante la instalación reparación y retirada No toque la aleta de aluminio de la unidad exterior Si lo hace podría lesionarse Si por algún motivo tuviera que tocar la aleta póngase primero guantes de protección y ropa de trabajo segura y luego empiece a trabajar No se suba encima de la unidad exterior ni coloque objetos sobre ell...

Page 17: ...e aislamiento Megger de 500 V para comprobar que la resistencia entre la sección con carga y la sección metálica sin carga sección de tierra es de 1 M o superior Si el valor de la resistencia es bajo esto se debe a un fallo como por ejemplo una fuga o una descarga eléctrica en el lado del usuario Al completar el trabajo de instalación verifique que no haya fugas de refrigerante y también la resist...

Page 18: ...ste trabalho Técnico de assistência qualificado O técnico de assistência qualificado é uma pessoa que instala repara mantém muda e elimina os aparelhos de ar condicionado fabricados pela Toshiba Carrier Corporation O técnico de assistência qualificado teve formação para instalar reparar manter mudar e eliminar os aparelhos de ar condicionado fabricados pela Toshiba Carrier Corporation ou alternati...

Page 19: ...io podem ocorrer choques eléctricos Coloque um sinal Trabalho em progresso junto ao disjuntor durante a realização de trabalhos de instalação manutenção reparação ou eliminação Existe um perigo de choques eléctricos se colocar o disjuntor na posição ON por engano Apenas um instalador qualificado 1 ou um técnico de assistência qualificado 1 pode efectuar o trabalho em altura utilizando um suporte d...

Page 20: ...oque o disjuntor eléctrico na posição OFF e contacte um técnico de assistência qualificado Tome as medidas necessárias para garantir que a corrente eléctrica não será ligada através da colocação do aviso fora de serviço junto ao disjuntor de serviço por exemplo até chegar o técnico de assistência qualificado Se continuar a utilizar o aparelho de ar condicionado com problemas pode provocar o aument...

Page 21: ...vereiste kennis voor deze ingrepen Bevoegd onderhouds monteur Een bevoegd onderhoudsmonteur is een persoon die zorgt voor het installeren repareren onderhouden verplaatsen en wegdoen van de airconditioners vervaardigd door de Toshiba Carrier Corporation Hij of zij is opgeleid voor het installeren repareren onderhouden verplaatsen en wegdoen van de airconditioners vervaardigd door de Toshiba Carrie...

Page 22: ...OFF stand Anders loopt u gevaar elektrische schokken te krijgen Plaats een bordje werk in uitvoering bij de stroomonderbreker tijdens het installeren het onderhoud het reparatiewerk of werk voor het verwijderen van het apparaat Als iemand per vergissing de stroomonderbreker in de positie AAN zet loopt u gevaar een elektrische schok te krijgen Alleen een bevoegd installateur 1 of een bevoegd onderh...

Page 23: ...rmt of wanneer er water uit lekt raakt u dan zelf de airconditioner niet aan maar zet u de stroomonderbreker in de OFF stand en neemt u contact op met een bevoegd onderhoudsmonteur Neem de nodige maatregelen om te voorkomen dat het apparaat wordt ingeschakeld schrijf bijvoorbeeld buiten gebruik dicht bij de stroomonderbreker tot de bevoegde onderhoudsmonteur arriveert Als de airconditioner in gebr...

Page 24: ... Corporation Toshiba Carrier Corporation Toshiba Carrier Corporation Toshiba Carrier Corporation Toshiba Carrier Corporation Toshiba Carrier Corporation Toshiba Carrier Corporation Toshiba Carrier Corporation 50 cm 150 370 335 mm 1115250101_EN indd 23 1115250101_EN indd 23 8 24 13 9 20 AM 8 24 13 9 20 AM ...

Page 25: ...icing CAUTION High temperature parts You might get burned when removing this panel CAUTION Do not touch the aluminum fins of the unit Doing so may result in injury CAUTION BURST HAZARD Open the service valves before the operation otherwise there might be the burst 1 1 1 4 OFF OFF 1 1 OFF ON 50 cm 1 1 ISO 14122 OFF R410A EN ID 1115250101_EN indd 24 1115250101_EN indd 24 8 24 13 9 20 AM 8 24 13 9 20...

Page 26: ... 25 50 GR 49 GR M10 M10 1 1 ON OFF 500 V Megger 1 M OFF 1 ON 1 1 1 HFC R410A R410A R410 A 1 6 R22 R410 A R410A R410 A 3 mm 1115250101_EN indd 25 1115250101_EN indd 25 8 24 13 9 20 AM 8 24 13 9 20 AM ...

Page 27: ... Corporation Toshiba Carrier Corporation Toshiba Carrier Corporation Toshiba Carrier Corporation Toshiba Carrier Corporation Toshiba Carrier Corporation Toshiba Carrier Corporation Toshiba Carrier Corporation 50 150 370 335 EN ID 1115250101_EN indd 26 1115250101_EN indd 26 8 24 13 9 21 AM 8 24 13 9 21 AM ...

Page 28: ...servicing CAUTION High temperature parts You might get burned when removing this panel CAUTION Do not touch the aluminum fins of the unit Doing so may result in injury CAUTION BURST HAZARD Open the service valves before the operation otherwise there might be the burst 1 1 1 4 OFF OFF 1 1 OFF ON 1 1 50 ISO 14122 OFF R410A 1115250101_EN indd 27 1115250101_EN indd 27 8 24 13 9 21 AM 8 24 13 9 21 AM ...

Page 29: ... 28 56 RU 55 RU 10 10 1 1 ON OFF 500 1 OFF 1 ON 1 1 1 R410A R410A R410A 1 6 R22 R410A R410A R410A 3 EN ID 1115250101_EN indd 28 1115250101_EN indd 28 8 24 13 9 21 AM 8 24 13 9 21 AM ...

Page 30: ...onnecting pipes use new and clean piping materials with high pressure fittings made for R410A only so that water and or dust does not enter Required tools equipment and precautions for use Prepare the tools and equipment listed in the following table before starting the installation work Newly prepared tools and equipment must be used exclusively Legend Prepared newly Use for R410A only Do not use...

Page 31: ...he gas and liquid sides 2 Pressurize the pipe with nitrogen gas charged from the service port to the design pressure 4 15 Mpa to conduct an airtight test 3 After the airtight test is completed evacuate the nitrogen gas Air purge To purge air use a vacuum pump Do not use refrigerant charged in the outdoor unit to purge air The air purge refrigerant is not contained in the outdoor unit Electrical wi...

Page 32: ...ow of a neighboring house A location where the operating noise of the outdoor unit is transmitted When the outdoor unit is installed in an elevated position be sure to secure its feet A location in which drain water poses any problems CAUTION 1 Install the outdoor unit in a location where the discharge air is not blocked 2 When an outdoor unit is installed in a location that is always exposed to s...

Page 33: ... for an outdoor unit with downward piping consider the piping work Set the out margin of the anchor bolt to 15 mm or less When water is to be drained through the drain hose attach the following drain nipple and waterproof rubber cap and use the drain hose Inner dia 16 mm sold on the market Also seal knockout hole and the screws securely with silicone material etc to prevent water from leaking Some...

Page 34: ...oes not come loose Refrigerant piping connection CAUTION Take note of these 4 important points below for piping work 1 Keep dust and moisture away from inside the connecting pipes 2 Tightly connect the connection between pipes and the unit 3 Evacuate the air in the connecting pipes using a VACUUM PUMP 4 Check for gas leaks at connection points Piping connection Flaring 1 Cut the pipe with a pipe c...

Page 35: ...ng torque 9 5 mm dia 34 to 42 3 4 to 4 2 NJI P 15 9 mm dia 63 to 77 6 3 to 7 7 NJI P Half union or packed valve Flare nut Internally threaded side Externally threaded side Fix with wrench Tighten with torque wrench Flare nut Piping valve Cap Tightened Loosened Valve at gas side Cover Do not apply refrigerant oil to the flared surface In correct Cap Cover Refrigerant pipe length Single Simultaneous...

Page 36: ...e compound pressure gauge indicates 101 kPa 76 cmHg 1 Close Handle Low completely Turn OFF the vacuum pump Leave the vacuum pump as it is for 1 or 2 minutes and check that the indicator of the compound pressure gauge does not return Open the valve stem or valve handle fully First at liquid side then gas side Disconnect the charge hose from the charge port Tighten the valve and caps of the charge p...

Page 37: ...ler Indoor unit Outdoor unit Circuit breaker For the air conditioner connect a power wire with the following specifications How to wire 1 Remove the mounting screws 2 pieces open the electrical control box cover 2 Connect the power supply wires and system interconnection wires to the terminal block of the electrical control box 3 Tighten the screws of the terminal block connect the wires matching ...

Page 38: ...ed As a general rule if an indoor unit is operated for about 8 hours daily the indoor outdoor units will need to be cleaned at least once every 3 months This cleaning and maintenance should be carried out by a qualified service person Failure to clean the indoor outdoor units regularly will result in poor performance icing water leaking and even compressor failure 12Air conditioner operating condi...

Page 39: ...indoor unit in the fan mode 2 Check that the LED displays are placed in their initial status If not place them in the initial status 3 Hold down SW01 for at least 5 seconds and check that D804 flashes slowly Fig 1 4 Press SW01 once to set the LED displays D800 to D805 to the refrigerant recovery LED display shown below Fig 2 Fig 1 ON OFF Slow flashing Fig 2 ON OFF Rapid flashing 5 Press SW02 to se...

Page 40: ...n step 6 is taken D800 D801 D802 D803 D804 D805 How to check the existing piping settings You can check whether the existing piping settings are enabled 1 Check that the LED displays are placed in their initial status If not place them in the initial status 2 Hold down SW01 for at least 5 seconds and check that D804 flashes slowly Fig 9 3 Press SW01 four times to set the LED displays D800 to D805 ...

Page 41: ...avy be sure to use new pipes for the refrigerant piping works 2 When the existing pipe thickness is thinner than the specified Pipe diameter and thickness be sure to use new pipes for the refrigerant piping works The operating pressure of R410A is high 1 6 times that of R22 and R407C If there is a scratch or dent on the pipe or a thinner pipe is used the pressure strength may be inadequate which m...

Page 42: ... Ø19 0 For R410A 9 1 13 2 16 6 19 7 24 0 For R22 9 0 13 0 16 2 19 4 23 3 Becomes a little larger for R410A A YES NO YES NO YES NO Is it possible to operate the existing air conditioner After the existing air conditioner is operated in cooling mode for approx 30 minutes or longer recover the refrigerant For cleaning the pipes and recovering oil Refrigerant recovery Pump down method Remove the exist...

Page 43: ...mthani 12000 Thailand Authorized Representative TCF holder Nick Ball Toshiba EMEA Engineering Director Toshiba Carrier UK Ltd Porsham Close Belliver Industrial Estate PLYMOUTH Devon PL6 7DB United Kingdom Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type RAV SM1104ATP E RAV SM1104ATJP E RAV SM1404ATP E RAV SM1404ATJP E Commercial name Digital Invert...

Page 44: ...nstalled requires a design that in the event of refrigerant gas leaking out its concentration will not exceed a set limit The refrigerant R410A which is used in the air conditioner is safe without the toxicity or combustibility of ammonia and is not restricted by laws to be imposed which protect the ozone layer However since it contains more than air it poses the risk of suffocation if its concent...

Page 45: ...MEMO 44 1115250101_cover indd 44 1115250101_cover indd 44 8 24 13 9 22 AM 8 24 13 9 22 AM ...

Page 46: ... 45 MEMO 1115250101_cover indd 45 1115250101_cover indd 45 8 24 13 9 22 AM 8 24 13 9 22 AM ...

Page 47: ...MEMO 46 1115250101_cover indd 46 1115250101_cover indd 46 8 24 13 9 22 AM 8 24 13 9 22 AM ...

Page 48: ...1115250101 1115250101_cover indd 47 1115250101_cover indd 47 8 24 13 9 22 AM 8 24 13 9 22 AM ...

Reviews: