Electrical work
WARNING
1
Using the specified wires, ensure that the
wires are connected, and fix wires securely
so that the external tension to the wires does
not affect the connecting part of the
terminals.
Incomplete connection or fixation may cause a
fire, etc.
2
Be sure to connect the earth wire.
(grounding work)
Incomplete grounding may lead to electric
shock.
Do not connect ground wires to gas pipes, water
pipes, lightning rods or ground wires for telephone
wires.
3
The appliance shall be installed in
accordance with national wiring regulations.
Capacity shortages of the power circuit or an
incomplete installation may cause an electric
shock or fire.
CAUTION
An installation fuse must be used for the power supply
line of this air conditioner.
Incorrect / incomplete wiring may lead to an electrical
fire or smoke.
Prepare an exclusive power supply for the air
conditioner.
This product can be connected to the mains power.
Fixed wire connections:
A switch that disconnects all poles and has a contact
separation of at least 3 mm must be incorporated in
the fixed wiring.
Be sure to use the cord clamps attached to the
product.
Do not damage or scratch the conductive core or inner
insulator of the power and system interconnection
wires when peeling them.
Use the power and system interconnection wires with
specified thicknesses, specified types and protective
devices required.
Remove the service panel, and you can see electric
parts on the front side.
A conduit pipe can be installed through the hole for
wiring. If the hole size does not fit the wiring pipe to
be used, drill the hole again to an appropriate size.
Be sure to clamp the power wires and system
interconnection wires with a banding band along the
connecting pipe so that the wires do not touch the
compressor or discharge pipe.
(The compressor and the discharge pipe become
hot.)
Wiring between indoor unit
and outdoor unit
The dashed lines show on-site wiring.
Connect the system interconnection wires to the
identical terminal numbers on the terminal block of
each unit.
Incorrect connection may cause a failure.
Electrical control
box cover
Cord clamp
Pipe hole
Service
panel
Screws
L
N
1
2
3
1
2
3
(system
interconnection wires)
Input power
Earth
(Main circuit)
Remote
controller
Indoor unit
Outdoor unit
Circuit
breaker
For the air conditioner, connect a power wire with the
following specifications.
How to wire
1. Remove the mounting screws (2 pieces), open the
electrical control box cover.
2. Connect the power supply wires and system
interconnection wires to the terminal block of the
electrical control box.
3. Tighten the screws of the terminal block, connect the
wires matching the terminal numbers (Do not apply
tension to the connecting section of the terminal
block.)
4. Close the electrical control box cover, attach the
mounting screws.
When connecting the system interconnection wire to
the outdoor unit terminal, prevent water from coming
into the outdoor unit.
Insulate the unsheathed cords (conductors) with
electrical insulation tape. Process them so that they
do not touch any electrical or metal parts.
For system interconnection wires, do not use a wire
joined to another on the way.
Use wires long enough to cover the entire length.
Stripping length power cord and system
interconnection wire
Wiring diagram
* For details on the remote controller wiring /
installation, refer to the Installation Manual enclosed
with the remote controller.
Single system
Simultaneous twin system
* Use 2-core shield wire (MVVS 0.5 to 2.0 mm² or
more) for the remote controller wiring in the
simultaneous twin system to prevent noise
problems. Be sure to connect both ends of the shield
wire to earth leads.
* Connect earth wires for each indoor unit in the
simultaneous twin system.
Model RAV-
SM110, SM140
Power supply
220-240 V~, 50 Hz
220 V~, 60 Hz
Maximum running current
22.8 A
Installation fuse rating
25 A (all types can be used)
Power supply wire
H07 RN-F or 60245 IEC 66
(2.5 mm
2
or more)
System interconnection
wires
H07 RN-F or 60245 IEC 66
(1.5 mm
2
or more)
L
N
1
2
3
Earth
screw
System
interconnection
wire
Power supply wire
To Indoor unit
terminal block
Power supply
terminal block
Earth
screw
Pipe valve
fixing plate
10
10
L N
40
10
50
50
10
30
1 2 3
Earth wire
System
interconnection
wire
Power supply
wire
(mm)
Earth wire
A B
1
1
2
2
3
3
N
L
Remote controller
Power supply
Remote controller wiring
Indoor side
System interconnection
wires
Outdoor side
A B
1
2
3
A B
1
1
2
2
3
3
N
L
Remote controller
Power supply
Remote controller
wiring
Indoor side
System
interconnection wires
Outdoor side
Remote
controller
inter-unit
wiring
Indoor
side
Indoor
power
inter-unit
wiring
EN
ID
1115250101_EN.indd 36
1115250101_EN.indd 36
8/24/13 9:21 AM
8/24/13 9:21 AM
Summary of Contents for RAV-SM1104ATJP-E
Page 45: ...MEMO 44 1115250101_cover indd 44 1115250101_cover indd 44 8 24 13 9 22 AM 8 24 13 9 22 AM ...
Page 46: ... 45 MEMO 1115250101_cover indd 45 1115250101_cover indd 45 8 24 13 9 22 AM 8 24 13 9 22 AM ...
Page 47: ...MEMO 46 1115250101_cover indd 46 1115250101_cover indd 46 8 24 13 9 22 AM 8 24 13 9 22 AM ...
Page 48: ...1115250101 1115250101_cover indd 47 1115250101_cover indd 47 8 24 13 9 22 AM 8 24 13 9 22 AM ...