Cause of operation
Current detection circuit
trouble
Open phase of 3-phase power supply
Ps sensor
trouble
Low pressure protective operation
Discharge temp.
trouble
∗
Discharge temp. (TD) over specified value
was detected.(1.6)
Case thermostat operation
∗
Abnormal overheat of compressor
High pressure SW system
trouble
Power supply voltage
trouble
High pressure protective operation
• During cooling operation, outdoor temp.
sensor (TL) detected temperature over
specified temp.
• During heating operation, indoor temp.
sensor (TC, TCJ) detected temperature over
specified temp.
Outdoor fan system
trouble
Short-circuit
trouble
of compressor
driving
element
Position detection circuit
trouble
Operation of diagnostic function
Check
code
Indoor
unit
H03
P05
F23
H06
P03
H04
P04
P05
P20
P22
P26
P29
Status of
air conditioner
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Condition
Displayed when
check code
is
detected
Displayed when
check code
is
detected
Displayed when
check code
is
detected
Displayed when
check code
is
detected
Displayed when
check code
is
detected
Displayed when
check code
is
detected
Displayed when
check code
is
detected
Displayed when
check code
is
detected
Displayed when
check code
is
detected
Displayed when
check code
is
detected
Displayed when
check code
is
detected
Displayed when
check code
is
detected
Judgment and measures
1. Check outdoor P.C. board.
(AC current detection circuit)
1. Check open phase of 3-phase power supply.
2. Black lead wire to be connected to CN03 of outdoor P. C.
board does not pass through T611.
1.
Check connection of Ps sensor connector.
2.
Check failure of Ps sensor.
3.
Check compressing power
trouble
of compressor.
4.
Check 4-way valve
trouble
.
5.
Check outdoor P.C. board
trouble
.
1.
Check service valves are fully opened.
(Gas side, Liquid side)
2.
Check clogging of outdoor PMV. (PMV1, 2)
3.
Check SV2 circuit.
4.
Check Ps sensor
trouble
.
5.
Check clogging of indoor filter.
6.
Check clogging of refrigerant pipe.
7.
Check of outdoor fan operation. (In heating mode)
8.
Check short of refrigerant.
1. Check refrigerating cycle (Gas leak)
2. Trouble of electronic expansion valve
3. Check discharge temp. sensor (TD).
1. Check case thermostat and connector.
2. Check gas leak, recharge
3. Check full open of service valve.
4. Check PMV (Pulse Motor Valve).
5. Check broken pipe.
1.
Check service valves are fully opened.
(Gas side, Liquid side)
2.
Check of outdoor fan operation.
3.
Check motor
trouble
of outdoor fan.
4.
Check clogging of outdoor PMV. (PMV1, 2)
5.
Check clogging of heat exchanger in indoor/outdoor units.
6.
Short-circuit status of suction/discharge air in outdoor unit.
7.
Check outdoor P.C. board
trouble
.
8.
Check fan system
trouble
(Cause of air volume drop) at
indoor side.
9.
Check PMV opening status in indoor unit.
1. Check power supply voltage.
1. Check outdoor heat exchanger sensor (TL).
2. Check indoor heat exchanger sensor (TC, TCJ).
3. Check full open of service valve.
4. Check indoor/outdoor fan.
5. Check PMV (Pulse Motor Valve).
6. Check clogging and short circuit of indoor/outdoor heat
exchanger.
7. Overcharge of refrigerant. Recharge
1. Check lock of fan motor.
2. Check power supply voltage between L2 and N.
3. Check outdoor P.C. board.
1.
When performing operation while taking-off compressor
wire, P26
trouble
occurs. Check control P.C. board.
2.
When performing operation while taking-off compressor
wire,
trouble
does not occur. (Compressor rare short)
1. Check control P.C. board.
- 48 -