TA-TSC
˚C
+3.0
+2.5
+2.0
+1.5
+1.0
+0.5
0
–0.5
HH
(HH)
H+ (HH)
H (HH)
L+ (H+)
L (H)
L (H)
L (L+)
D
C
B
A
E
F
G
[-0.5]
–1.0
[
0
]
0
[+0.5]
+1.0
[+0.1]
+2.0
[+
1
.
5
]
+3.0
[+2.0]
+4.0
L (L+)
L+ (H)
H (H+)
HH
(HH)
H+
(HH)
E
D
C
B
A
No.
6
Item
Fan speed control
Outline of specifications
1)
Operation with (HH), (H), (L) or [AUTO] mode is carried
out by the command from the remote controller.
2)
When the fan speed mode [AUTO] is selected, the fan
speed varies by the difference between
TA
and
TS
.
<COOL>
• Controlling
work using thermostat of remote controller is
same as the case of using body thermostat.
• If the fan speed has
changed automatically
, it is not
changed
for 3 minutes. However when the air volume is
exchanged,
the fan speed changes.
• When cooling operation started,
the fan speed will be
selected along a down arrow in figure
.
•
When "TA-TSC" is just on boundary the fan speed won't
change
.
•
( ) indicated the fan speed at automatic cooling operation
.
<HEAT>
the value with [ ] indicates the
temperature
at using remote
controller thermostat.
the value without [ ] indicates the
temperature
at using body
thermostat of indoor unit.
• If the fan speed has changed
automatically
, it is not
changed
for 1 minute.
•
When heating operation starts,
the fan speed will be
selected along an up arrow in figure
.
•
When 'TSH-TA' is just on boundary, the fan speed won't
change
.
•
( ) indicates the fan speed at automatic heating operation
.
• In
TC
≥
60°C, the fan speed increases by 1 step.
Remarks
HH > H+ > H > L+ >
L > UL
TC
:
Indoor heat
exchanger sensor
temperature
TSH-TA
˚C
- 29 -