No.
⑨
Part name
Procedure
Remarks
Heat
exchanger
screw
D
Right side panel
Heat exchanger
Left side panel
Screw A
1.
Detachment
1)
Recover the refrigerant gas and then remove
the refrigerant pipe of the indoor unit.
2)
Perform 1 of ⑦ to remove the drain pan.
3)
Remove the screw A (M4 x 0.4" (10mm), 7 pcs)
and remove the Left side panel.
4)
After performing 1) and 3) of 1 of ⑧ ,
withdraw the wire of the sensor from the
bushing to the heat exchanger side.
5)
Remove the screw B (M4 x 0.4" (10mm), 3 pcs)
and remove the evaporator partition (back).
6)
Remove the screw C (M4 x 0.4" (10mm), 4 pcs)
and remove the evaporator partition (down).
7)
Remove the screw D (M4 x 0.4" (10mm), 5 pcs)
of the right side panel.
8)
While holding the heat exchanger, remove the
screw E (M4 x 0.4" (10mm), 2 pcs) and then
take out the heat exchanger slowly.
Evaporator partition (back
Screw B
Screw E
Bushing
Screw C
Screw
E
Evaporator partition
(down)
2. Attachment
1)
Attach the heat exchanger to the original position.
Screw E (M4 x 0.4" (10mm), 2 pcs)
2)
Fix the screw D on the right side panel as before.
Screw D (M4 x 0.4" (10mm), 5 pcs)
3)
Attach the evaporator partition (down) as before.
Screw C (M4 x0.4" (10mm), 4 pcs)
4)
Attach the evaporator partition (back) as before.
Screw B (M4 x 0.4" (10mm), 3 pcs)
5)
Perform 1) , 3) and 4) of 2 of ⑧ to attach the
sensor conector and electrical parts box cover .
6)
Attach the Left side panel as before.
Screw A (M4 x 0.4" (10mm), 7 pcs)
7)
Perform 2 of ⑦ to attach the drain pan and
bottom plate (drain side).
- 94 -