Concealed Duct Static Pressure Type for Australia, New zealand
(50Hz)
Indoor Unit
RAV-
R
M224
1
DTP-E
R
M280
1
DTP-E
Outdoor Unit
RAV-
SM2244AT8-A1
SM2804AT8-A1
Cooling capacity …Note 1
(kW)
16.8
20.0
Heating capacity …Note 1
(kW)
22.4
27.0
Electrical
Cooling
Indoor Unit
Power supply
1phase 50Hz 230V-240V
characteristics
Running current (230V-240V)
(A)
2.80
-
2.68
3.75
-
3.59
(factory setting)
Power consumption
(kW)
0.530
0.785
Power factor
(-)
0.82
0.91
Outdoor Unit
Power supply
3-phase 4 wires 50Hz 400-415V
Running current (400V-415V)
(A)
7.86
-
7.58
9.16
-
8.83
Power consumption
(kW)
4.71
5.62
Power factor
(-)
0.86
0.89
Total
Power consumption (min-max)
(kW)
5.05 (2.63-7.60)
6.10 (2.68-12.20)
EER …Note 2
3.33
3.28
Heating
Indoor Unit
Power supply
1phase 50Hz 230V-240V
Running current (230V-240V)
(A)
2.80
-
2.68
3.75
-
3.59
Power consumption
(kW)
0.530
0.785
Power factor
(-)
0.82
0.91
Outdoor Unit
Power supply
3-phase 4 wires 50Hz 400-415V
Running current (400V-415V)
(A)
8.83
-
8.51
10.66
-
10.27
Power consumption
(kW)
5.51
6.51
Power factor
(-)
0.90
0.88
Total
Power consumption (min-max)
(kW)
5.91 (2.32-7.02)
7.20 (2.55-9.32)
COP …Note 2
3.79
3.75
Maximum Indoor Unit
starting c
u
rrent
(A)
8.15
8.15
Current
Outdoor Unit
starting c
u
rrent
(A)
18.0
20.0
Appearance
Zinc hot dipping steel plate
Dimension
Height
(mm)
448
Width
(mm)
1400
Depth
(mm)
900
Weight
(kg)
97
Heat exchanger
Finned tube
Soundproof / Heat-insulating m
a
terial
Polyeth
y
lene foam
Fan unit
Fan
Centrifugal fan
Standard air flow
3,800
4,800
(Med./Low)
(3,200 / 2,500)
(4,200 / 3,500)
Motor output
(kW)
1kW * 1pc
External static pressure (factory setting)
(Pa)
150
External static pressure range
(Pa)
50-83-117-150-183-217-250 (7steps)
Controller
Remote controller
Air filter
Sold separately (TCB-LK2801DP-E)
Drain pump
Sold separately (TCB-DP40DPE)
Connecting
Gas side
(mm)
Φ28.6
pipe
Liquid side
(mm)
Φ12.7
Drain port
(mm)
25(Polyvinyl chloride tube)
(dB(A))
44 / 40 / 36
46 / 42 / 38
Sound power level (High/Med./Low)
(dB(A))
79 / 75 / 71
81 / 77 / 73
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on the reference piping.
The reference piping consists of 7.5m piping connected with 0 meter height.
Note 2 :
The EER and COP are measured under conditions spe
c
ified by BS EN14511(2013)
External static pressure is d
i
fferent from factory setting.
Note 3 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated valves due to the effects of external sound.
Note: Rated conditions Cooling: Indoor air temperature 27
℃
DB/19
℃
WB, Outdoor air temperature 35
℃
DB
Heating: Indoor air temperature 20
℃
DB, Outdoor air temperature 7
℃
DB/6
℃
WB
(m3/h)
Sound pressure level (High/Med./Low) …Note 3 (factory setting)
Model name
- 18 -