No.
Item
Outline of specifications
Remarks
1) This function is intended for the cold latitudes and performs
objective heating operation 8°C heating operation).
2) This function is valid only for combination with the outdoor units.
3) Using the indoor CODE No. [D1] (1 bit), Valid/Invalid of this
function is set up at the customer’s side.
∗
The setup by CODE No. is Invalid [0]/Valid [1] and Invalid
[0] has been set at the shipment.
4) This operation is the heating operation which sets
8°C as the setup temperature of the target.
5) This function starts operation by pushing temperature button
during heating operation; besides by pushing
button for 4 seconds or more after temperature reached the
minimum set temperature.
6) To stop/release this operation, select and execute one from
the following operations.
Q
Push
button:
Heating operation 18°C setting) continues.
R
Push [START/STOP] button:
Air conditioner stops.
(Heating 18°C operation at the next start)
S
Push
MODE
:
Other operation mode is selected and the operation
continues.
7) As the setup temperature is 8°C and the human
heating is not targeted, the cold air discharge preventive
control (Item 7) is made invalid to suppress the intermittent
operation.
8) The settings of the air direction and air volume are
changeable during this operation.
9) The indoor fan stops to protect the compressor for
2 minutes after start of heating operation (Thermo-ON) by
this function.
In a group connection,
if there is even one
combination with other
unit, “This function is not
provided.” is displayed.
The setup temperature
jumps from [18] to [8].
2
2
8°C
heating/
Frost protective
operation
(Wired remote
controller specific
operations)
2
3
Hi POWER
operation
(Wireless remote
controller specific
operations)
When you push the Hi POWER button during cooling,
heating or AUTO, the air conditioner will start the following
operation.
• Cooling operation
Performs the cooling operation at 1°C lower than
the setting temperature.
Only when the fan speed before the Hi POWER operation
is not high, the fan speed will be increased.
• Heating operation
Performs the heating operation at 2°C higher
than the setting temperature.
Only when the fan speed before the Hi POWER operation
is not high, the fan speed will be increased.
• [Hi POWER] Display
FILE NO. SVM-18059
- 37 -
Summary of Contents for RAV-GM301ATP-E
Page 113: ...TOSHIBA CARRIER CORPORATION ...