No.
6
Item
Fan speed control
(Continued)
Outline of specifications
Remarks
“PRE-HEAT ”
indication
7
Cool air discharge
preventive control
1) In heating operation, the indoor fan is controlled based on
the detected temperature of Tc sensor or Tcj sensor. As
shown below, the upper limit of the revolution frequency is
restricted.
However B zone is assumed as C zone for
6 minutes and after when the compressor activated.
In defrost operation, the control value of Tc or Tcj is shifted
by 6°C.
In D and E zones, the
priority is given to air
volume selection
setup of remote
controller.
Tc, Tcj
˚C
32
30
28
26
20
16
HH
H
L
UL
OFF
E zone
D zone
C zone
B zone
A zone
Ta
˚C
HH
HH+
α
47
42
3) When thermo sensor turns OFF during heating, the fan
speed mode becomes UL ( weak).
4) When Ta is 25°C or above at the beginning of HEAT
operation or when canceling defrost mode, H or HH mode
continues for 1 minute from the time when Tc enters zone
E. (Following figure.)
5) The HH fan speed for auto cooling/heating is set to a
speed higher than that for normal cooling/heating.
However, it varies depending on the temperature difference
of Tc during auto heating.
Fan speed [rpm]
COOL
HEAT
RM301
RM401
RM561
RM801
HH
1040
1080
1020
1080
HH
1040
1080
1020
1080
H+
H+
950
1000
960
1020
H+
890
950
920
980
H
870
920
920
980
L+
830
870
860
860
L+
L
780
800
830
830
L+
740
760
800
800
UL
UL
500
500
500
500
FILE NO. SVM-18059
- 31 -