[P12 error]
Does fan rotate?
Turn OFF the breaker.
Change
fan speed to HIGH.
Does
fan speed increase?
Fan motor
is normal.
Turn it ON 10 seconds after.
Does fan stop
with operation OFF?
Start cooling
with LOW fan speed.
Does cross flow fan
rotate normally by hand?
Stop operation and turn OFF breaker.
Disconnect CN210, turn ON breaker again,
and then stop operation using remote controller.
Stop operation and turn off the breaker.
Discnnect CN210, turn on the breaker,
and then stop operation using remote controller.
Is min. 1V DC present
between CN210 pin
+ and
– ?
Is min. 280V DC present
between CN210 pin
+ and
– ?
Is min. 15V DC present
between CN210 pin
+ and
–
with motor connected?
Is min. 280V DC present
between CN210 pin
+ and
– ?
Operate indoor unit (except heating)
by remote controller.
Is min. 1V DC present
between CN210 pin
+ and
– ?
(Measure within 15 seconds.)
Rotate the fan by hand
with operation OFF.
Is 0 to 15V DC (rev return signal)
generated between
CN210 pin
+ and
– ?
Operate indoor unit (except heating)
by remote controller.
Is min. 1V DC present between
CN210 pin
+ and
– ?
(Measure within 15 seconds.)
Replace indoor unit
MCC-1
696
P.C. board.
Replace indoor unit
MCC-1
696
P.C. board.
Replace indoor unit
MCC-1
696
P.C. board.
Replace indoor unit
MCC-1
696
P.C. board.
Replace indoor unit
MCC-1
696
P.C. board.
Replace
indoor unit fan motor.
Replace
indoor unit fan motor.
Replace
indoor unit fan motor.
Replace
indoor unit fan motor.
Repair cross
flow fan shaft.
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES