10-6. Monitor Function of Remote Controller Switch
n
Calling of sensor temperature display
<Contents>
Each data of the remote controller, indoor unit and outdoor unit can be understood by calling the service
monitor mode from the remote controller.
∗
1 Header indoor unit only under group control.
<Procedure>
1
Push
TEST
+
CL
buttons simultaneously for 4 seconds to
call the service monitor mode.
The service monitor goes on, the master indoor unit No. is
displayed at first and then the temperature of CODE No.
is displayed.
ò
2
Push temperature set
TEMP.
buttons and then change
the CODE No. of data to be monitored.
The CODE No. list is shown below.
Indoor unit data
CODE No.
00
01
02
03
04
Data name
Room temperature under control
∗
1
Room temperature
(Remote controller)
Indoor suction temperature (TA)
Indoor heat exchanger (Coil)
temperature (TCJ)
Indoor heat exchanger (Coil)
temperature (TC)
Outdoor unit data
CODE No.
60
61
62
63
65
Data name
Outdoor heat exchanger (Coil) temperature (TE)
Outside temperature (TO)
Compressor discharge temperature (TD)
Compressor suction temperature (TS)
Heat sink temperature (TH)
ò
3
Push
UNIT LOUVER
button to select the indoor unit to be monitored.
Each data of the indoor unit and its outdoor units can be monitored.
ò
4
Pushing
TEST
button returns the status to the usual display.
<Operation procedure>
1 2 3 4
Returned to usual display
2
4
1
3
SET
TIME
TIMER SET
TEST
FILTER
LL
RESET
TEMP.
CL
FAN
SAVE
A
A
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
T
FILE NO. SVM-18059
- 71 -