No.
Part name
Procedure
Remarks
5
P.C.Board
(for control
and 1 fan
motor drive)
MCC-1626
1. Detachment
1) Carry out work of 1 of
.
WARNING
Never disassemble the inverter for 3
minutes after power has been turned off
because an electric shock may be caused.
2. Attachment
1) Mount the P.C.board to inverter box.
2) Mount the individual components in
the opposite procedure to that during
detachment.
CAUTION
Be sure that all the connectors are
connected correctly and securely inserted.
If the components on the P.C.board were
bent during this procedure, straighten
them so they do not touch other parts.
CN03, CN04, CN05
P.C.Board (For control and 1 fan motor drive) MCC-1626
4
2) After take off ASM-BOX-INV from Unit.
- Take off the connectors that
connecting from control board.
*Take off connectors by pulling the
connector body. Do not pull the wire.
*connectors should be remove after
unlocking the housing section.
CN02: Power supply (2P: White)
CN03: Connection with indoor unit (3P: White)
CN04: Power supply (3P: Red)
CN05: Power supply (2P: Red)
CN502: Relay output (2P: white)
CN851: UART communication (6P: Red)
3) Take off the P.C.Board (for control and
P.C.Board
(for 2 fan
motor drive)
CN01: UART communication (5P: White)
CN02: UART communication (5P: White)
CN100: Power supply (1P: Yellow)
CN101: Power supply (1P: Blue)
4) Take off the P.C.Board (for 2 fan
motor drive) from the 4 PCB mounts.
MCC-1603
CN851
CN502
CN02
CN100
CN101
CN01, CN02
st
1
st
fan
motor
drive)
from
the
6
PCB
mounts.
nd
nd
P.C.Board (For 2 fan motor drive) MCC-1603
st
nd
- 90 -