8-2-3. Check Code List (Outdoor)
: Go on,
◎
: Flash,
: Go off
ALT (Alternate): Alternate flashing when there are two flashing LED SIM (Simultaneous): Simultaneous flashing when there are two fl
ashing LED
Central Control indication
Remote Controller indication
Sensor lamp part
Representative defective position
Detection
Explanation of error contents
Automatic
Reset
Operation continuation
Block indication
Operation
Timer Ready
Flash
19
F04
◎
◎ ○
ALT
Outdoor unit Discharge temp. sensor (TD) error
Outdoor
Disconnection, short of discharge temp. sensor (TD) was detected
××
18
F06
◎
◎ ○
ALT
Outdoor unit Heat exchanger temp. sensor (TE) error
Outdoor
Disconnection, short of heat exchanger temp. sensor (TE) was detec
ted.
××
1b
F08
◎
◎ ○
ALT
Outdoor unit Outside air temp. sensor (TO) error
Outdoor
Disconnection, short of outside air temp. sensor (TO) was detected.
○○
A2
F12
◎
◎ ○
ALT
Outdoor unit Suction temp. sensor (TS) error
Outdoor
Disconnection, short of suction temp. sensor (TS) was detected.
××
43
F13
◎
◎ ○
ALT
Outdoor unit Heat sink temp. sensor (TH) error
Outdoor
Disconnection, short of heat sink temp. sensor (TH) (P.C.board installe
d) was detected.
××
18
F15
◎
◎ ○
ALT
Outdoor unit Miss-mounting of temp. sensor (TE, TS)
Outdoor
Miss-mounting of outdoor heat exchanger temp. sensor (TE) and suct
ion temp. sensor(TS) was detected.
××
1C
F31
◎
◎ ○
SIM
Outdoor unit EEPROM error
Outdoor
Outdoor P.C.board part (EEPROM) error was detected.
××
1F
H01
●
◎ ●
Outdoor unit Compressor break down
Outdoor
Reached release point at min-Hz during compressor operating.
××
1d
H02
●
◎ ●
Outdoor unit Compressor lock
Outdoor
Compressor lock was detected.
××
17
H03
●
◎ ●
Outdoor unit Current detection circuit error
Outdoor
Current detection circuit error.
××
44
H04
●
◎ ●
Outdoor unit case thermostat worked
Outdoor
Case thermostat worked.
××
88
L10
◎
○ ◎
SIM
Outdoor unit Unset model type of service P.C.board
Outdoor
When outdoor service P.C.board was used, model type select jumper s
etting was inappropriate.
××
1C
L29
◎
○ ◎
SIM
Outdoor unit Communication error between MCUs
Outdoor
Communication error between MCUs, EEPROM MCC-1603
error, EEPROM MCC-1627 error.
××
1E
P03
◎
● ◎
ALT
Outdoor unit Discharge temp. error
Outdoor
Error was detected by discharge temp. release control.
××
21
P04
◎
● ◎
ALT
Outdoor unit High pressure SW system error
Outdoor
High pressure protection switch worked.
××
AF
P05
◎
● ◎
ALT
Power supply voltage error
Outdoor
Power supply voltage error. Open phase detection error.
××
1C
P07
◎
● ◎
ALT
Outdoor unit Heat sink overheat error
Outdoor
Abnormal overheat was detected by outdoor heat sink temp. sensor.
××
AE
P15
◎
● ◎
ALT
Gas leak detection
Outdoor
Abnormal overheat of discharge temp. or suction temp. was detected.
××
22
P20
◎
● ◎
ALT
Outdoor High pressure protective operation
Outdoor
Error was detected by high release control from indoor / outdoor heat excha
nger temp. sensor.
××
1A
P22
◎
● ◎
ALT
Outdoor unit Outdoor fan system error
Outdoor
Error (Over-current, lock, overheat, etc.) was detected on outdoor fan drive cir
cuit.
××
14
P26
◎
● ◎
ALT
Outdoor unit Short-circuit of compressor drive element
Outdoor
Short-circuited protective operation of compressor drive circui
t element (G-Tr / IGBT) worked.
××
16
P29
◎
● ◎
ALT
Outdoor unit Position detection circuit error
Outdoor
Position detection error of compressor motor was detected.
××
18
F07
ALT
Outdoor
unit
Heat
exchanger
t t
emp.
sensor
(T
L)
error
Outdoor
Disconnection, short of outside heat exchanger temp. Sensor (TL)
was detected.
×
×
08
P19
4-way valve inverse error
Indoor Outdoor
In heating operation, error was detected by temp. down of indoor heat exchanger or temp. up of TE, TS.
ALT
○
×
◎
● ◎
◎
◎ ○