3. Current release control
The output frequency and the output voltage are controlled by AC current value detected by T620 and T621
on the outdoor P.C. board so that input current of the inverter does not exceed the specified value.
I
1
I
1 – 0.5
Current [A]
Frequency down
Normal operation
Hold
Hold
4. Outdoor fan control
Allocations of fan tap revolutions [rpm]
W1
W2
W3
W4
W5
W6
W7
W8
W9
WA
WB
WC
WD
WE
WF
250
280
330
360
410
460
520
580
650
700
760
830
900
940
980
4-1. Cooling fan control
1) An outdoor fan is controlled by TE sensor, TO sensor and operation frequency. An outdoor fan is
controlled at 1-tap interval of DC fan control.
2) At the start time, the fan is fixed for 60 seconds only with the maximum fan tap corresponded to the zone
in the following table but it is controlled with TE sensor temperature after then.
+
1 tap / 20 sec (Up to the maximum
rotational frequency of each zone)
Rotational frequency hold
– 1 tap / 20 sec
(Up to the minimum rotational
frequency of each zone)
WF tap
TE
55°C
38°C
35°C
58°C
COOL
I
1 value [A]
16.7
Temp. range
Under
20.4
Hz
Over
20.4
,
under
45.0
Hz
Over
45.0
Hz
MIN.
MAX.
MIN.
MAX.
MIN.
MAX.
38°C
≤
TO
W6
WD
W8
WF
WA
WF
29°C
≤
TO < 38°C
W5
WC
W7
WE
W9
WF
15°C
≤
TO < 29°C
W3
W7
W5
W9
W7
WB
5°C
≤
TO < 15°C
W2
W5
W4
W7
W6
W9
0°C
≤
TO < 5°C
W1
W3
W3
W5
W4
W7
– 4°C
≤
TO < 0°C
W1
W2
W2
W4
W3
W5
TO < – 4°C
OFF
OFF
OFF
W2
OFF
W3
TO error
OFF
WD
OFF
WF
OFF
WF
280
280
330
340
410
440
500
560
600
660
700
780
860
940
980
Fan 1
Fan 2