RAS-B13J2KVSG-E
, RAS-B13N4KVSG-E
/ RAS-13J2AVSG-E
NOTE :
•
P
Pressure measurement
Gauge attaching port
Vacuum pump connecting port
Deoxidized copper pipe
Outer dia. : 9.52mm(16)
Thickness : 0.8mm
NOTE :
Gas leak check position
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
T1
TO
Temp. measurement
INDOOR UNIT
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe
Outer dia. : 6.35mm
Thickness : 0.8mm
Sectional shape
of heat insulator
Allowable
height
difference : 12m
Allo
w
ab
le pipe length
Strainer
Pulse Modulating
valve at liquid side
Ø1.2 x 80
Ø1.2 x 80
TD
4-way valve
Compressor
KSK89D53UFZ
TS
T2
Outdoor heat
exchanger
Split capillary
Temp. measurement
Refrigerant amount : 0.80kg
Propeller fan
OUTDOOR UNIT
Muffler
Muffler
TE
TC
TA
The maximum pipe length of this air conditioner is 15 m. When the pipe length exceeds 15m, the additional
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 100g)
Max. : 20m
Min. : 2m
Chargeless : 15m
TCJ
Strainer
- 25 -