7-2. Operation Data
<Cooling>
NOTES :
Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
Model name
Standard
Indoor
Outdoor Compressor
pressure
fan mode fan mode revolution
Indoor Outdoor
P (MPa) T1 (°C)
T2 (°C)
(rps)
27/19
35/-
RAS-B10J2KVSG-E
RAS-B10N4KVSG-E
1.1 to 1.2
12 to 13 45 to 46
High
High
38
RAS-B13J2KVSG-E
RAS-B13N4KVSG-E
1.0 to 1.1 10 to 12 48 to 50
High
High
67
Tempeature
condition(°C)
Heat exchanger
pipe temp.
Connecting
piping
(m)
5.0
RAS-B16J2KVSG-E
RAS-B16N4KVSG-E
1.0 to 1.1 9 to 10 49 to 51
High
High
78
Model name
Standard
Indoor
Outdoor Compressor
pressure
fan mode fan mode revolution
Indoor Outdoor
P (MPa) T1 (°C)
T2 (°C)
(rps)
20/-
7/6
RAS-B07J2KVSG-E
RAS-B07N4KVSG-E
2.4 to 2.6 39 to 40
1 to 2
High
High
54
RAS-B13J2KVSG-E
RAS-B13N4KVSG-E
2.6 to 2.8 42 to 44 1 to 2
High
High
78
Tempeature
condition(°C)
Heat exchanger
pipe temp.
Connecting
piping
(m)
RAS-B16J2KVSG-E
RAS-B16N4KVSG-E
2.8 to 3.0 44 to 46 1 to 2
High
High
90
<Heating>
RAS-B07J2KVSG-E
RAS-B07N4KVSG-E
12 to 13 45 to 46
1.1 to 1.2
High
High
50
RAS-B10J2KVSG-E
RAS-B10N4KVSG-E
2.4 to 2.6 39 to 40 1 to 2
High
High
70
5.0
- 27 -