Item
Operation flow and applicable data,etc
Description
19
. Fireplace
Operation
Fireplace button on remote controller is
pressed.
Fireplace 1:
Cancel cold draft prevention control and fan
speed depend on user require base on basic
control.
Fireplace 2:
Cold draft prevention control is active with super
low fan speed (640 rpm).
Keep air circulation during other heat
source applied.
Note:
With Fireplace operation on heating
mode indoor unit always runs and cold
air breezing might be occurred.
Fireplace Operation
2
0
. 8
C heating /
Frost
protective
operation
Button on remote controller is pressed.
Set temperature is performed for 5
C to 13
C
and no cold draft prevention control.
Intended for cold latitudes and
performs objective heating operation.
8
C heating operation
8°C
Normal
operation
8°C
Normal
operation
Fireplace#1
Fireplace#
2
Fireplace#1
Fireplace#
2
2
1
. QUIET mode
Quiet mode is the system which, control the
revolving speed of indoor fan to work
constantly at lower than speed L. In addition,
noise level of indoor unit is less than usual.
Remarks :
1.
2.
Quiet mode is unable to work in dry mode.
Quiet mode is appropriate to work with less
cooling load and less heating load condition.
Because of the fan speed L- may cause not
enough the cooling capacity or heating
capacity.
The "Quiet mode" selected from [ ] button;
- The fan of the indoor unit will be restricted the revolving
speed at speed UL.
- The compressor speed is controlled as show in
the figure.
] button is
The "Quiet mode" is canceled by [
pressed to select other speed.
Model
07k
10k
13k
16k
Cool min (Hz)
20.4
20.4
20.4
20.4
Quiet Cool (Hz)
30.6
30.6
34.8
45.0
Heat min (Hz)
20.4
20.4
20.4
20.4
Quiet Heat (Hz)
30.6
30.6
55.2
55.2
- 50 -