background image

5

Outdoor Unit

Installation Manual

 

WARNING

•  If you detect any damage, do not install the unit. Contact your supplying dealer immediately. 
•  Never modify this unit by removing any of the safety guards or bypassing any of the safety 

interlock switches. 

•  Do not wash air conditioners with pressure washers.

Electric leaks may cause electric shocks or fires. 

•  Be sure to comply with local regulations/codes when running the wire from the outdoor unit 

to the indoor unit. (Size of wire and wiring method etc.) 

•  When installing the air conditioner in a small room, provide appropriate measures to 

ensure that the concentration of refrigerant leakage occur in the room does not exceed the 
critical level. It is not dangerous refrigerant; it has not toxicity or combustibility. However, 
a concentration above 0.3 kg/m

3

 as criterion still causes suffocation. The volume of 

refrigerant charged to the Multi System air conditioner is more than the volume charged to a 
conventional individual system.

•  Make sure drain hose insulation if cooling operation is used at sub-zero ambient 

temperature.

 

CAUTION

•  Please read this installation manual carefully before installing the unit. It contains further 

important instructions for proper installation. 

•  Exposure of unit to water or other moisture before installation could result in electric 

shock. Do not store it in a wet basement or expose to rain or water. 

•  After unpacking the unit, examine it carefully for possible damage. 

•  Do not install in a place that can increase the vibration of the unit. Do not install in a place 

that can amplify the noise level of the unit or where noise and discharged air might disturb 

neighbours. 

•  This appliance must be connected to the main power supply by means of a circuit breaker 

depending on the place where the unit is installed. Failure to do so may cause electrical 

shock. 

•  Follow the instructions in this installation manual to arrange the drain pipe for proper 

drainage from the unit. Ensure that drained water is discharged. Improper drainage can 

result in water leakage, causing water damage to furniture. 

•  Tighten the flare nut with a torque wrench using the prescribed method. Do not apply 

excess torque. Otherwise, the nut may crack after a long period of usage and it may 

cause the leakage of refrigerant. 

•  Wear gloves (heavy gloves such as cotton gloves) for installation work. Failure to do so 

may cause personal injury when handling parts with sharp edges. 

•  Do not touch the air intake section or the aluminium fins of the outdoor unit. It may cause 

injury. 

•  Do not install the outdoor unit in a place which can be a nest for small animals. Small 

animals could enter and contact internal electrical parts, causing a failure or fire. 

•  Request the user to keep the place around the unit tidy and clean. 

•  Make sure to conduct a test run after the installation work, and explain how to use and 

maintain the unit to the customer in accordance with the manual. Ask the customer to 

keep the operation manual along with the installation manual.

•  Do not climb onto or place objects on top of the outdoor unit. You may fall or the objects 

may fall off of the outdoor unit and result in injury.

Requirement of report to the local power supplier 

Please make absolutely sure that the installation of this appliance is reported to the local 

power supplier before installation. If you experience any problems or if the installation is not 

accepted by the supplier, the service agency will take adequate countermeasures.

1116791101_EN.indd   5

1116791101_EN.indd   5

2/3/58 BE   2:20 PM

2/3/58 BE   2:20 PM

Summary of Contents for RAS-3M26S3AV-A

Page 1: ... TYPE Installation Manual Outdoor Unit Model name RAS 5M34S3AV A RAS 4M27S3AV A RAS 3M26S3AV A NOTE Descriptions about operations for the E unit in this manual are not applicable to RAS 4M27S3AV A Descriptions about operations for the D unit and the E unit in this manual are not applicable to RAS 3M26S3AV A 1116791101 1116791101_EN indd c1 1116791101_EN indd c1 2 3 58 BE 2 20 PM 2 3 58 BE 2 20 PM ...

Page 2: ...evice and Outdoor Unit 11 10 Test run 14 Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the outdoor unit For installation of the indoor unit refer to the Installation Manual attached to the indoor unit IMPORTANT NOTICE For details on how to install the indoor units refer to the installation manual accompanying t...

Page 3: ...ING It indicates that incorrect use of this unit may cause severe injury or death CAUTION It indicates that incorrect use of this unit may cause personal injury 2 or property damage 3 1 A severe injury refers to blindness injury burns hot or cold electrical shock bone fracture or poisoning that leaves after effects and requires hospitalization or extended out patient treatment 2 Personal injury me...

Page 4: ...wiring Turn off main power supply before attempting any electrical work Make sure all power switches are off Failure to do so may cause electric shock Connect the connecting cables correctly If the connecting cables are connected wrongly electric parts may be damaged Check the earth wire that it is not broken or disconnected before installation Do not install near concentrations of combustible gas...

Page 5: ...do so may cause the unit to fall water leakage fire or electrical shock After the installation work ensure that there is no leakage of refrigerant gas If the refrigerant gas leaks out of the pipe into the room and is heated by fire or something else from a fan heater stove or gas range it causes generation of poisonous gas Make sure the equipment is properly earthed Do not connect the earth wire t...

Page 6: ... be connected to the main power supply by means of a circuit breaker depending on the place where the unit is installed Failure to do so may cause electrical shock Follow the instructions in this installation manual to arrange the drain pipe for proper drainage from the unit Ensure that drained water is discharged Improper drainage can result in water leakage causing water damage to furniture Tigh...

Page 7: ...ditioner differs depending on the combination of the indoor units which are operated The information in this specifications table applies for the combinations with the catalogue For operation read the owner s manual packed with the indoor unit Equipment complying with IEC 61000 3 12 1 If the air conditioner is used in conditions other than the above the safety protection functions may be activated...

Page 8: ...ioner under low outside temperature conditions Outside temp 5 C or lower In COOL mode prepare a duct or wind shield so that it is not affected by the wind Necessary Space for Installation If you need to install the outdoor unit in a location where there are some obstructions or a wall secure sufficient space as shown in the figure below The cooling heating effect may be reduced by 10 Upper side vi...

Page 9: ... core Setting Pin using the charge hose NOTE If a control valve or charge valve is attached to the charge hose leak of R410A refrigerant can be avoided 2 Open the Handle Low of the gauge manifold valve fully then operate the vacuum pump Loosen the flare nut of the at the gas end a little to make sure that air is taken in then tighten the nut If you find air is not taken in make sure that the charg...

Page 10: ...rming Additional Installation of an Indoor Unit 1 Collect refrigerant from the outdoor unit 2 Turn off the circuit breaker 3 Perform additional installation referring to the procedure from Refrigerant Piping Connection on the previous page Pump down Operation Recovering refrigerant CAUTION Since the forcible running for collecting refrigerant stops automatically after 10 minutes finish collecting ...

Page 11: ... terminal numbers on the terminal block of each unit Incorrect connection may cause a failure 1 Detach the front panel from the outdoor unit 2 Remove the cord clamp 3 Connect the wires for the power source and each indoor unit Connect the connecting cable to the terminal as identified by the matching numbers on the terminal block of the indoor and the outdoor unit 4 Fix the wiring connections for ...

Page 12: ... connecting wire is incorrect electric parts may be damaged Ensure that all terminals are securely fixed so preventing any external forces having a negative effect on the terminals Do not connect the DRED mains cable to the terminal block of the outdoor unit Power supply and Indoor Outdoor connecting Improper installation may result in fire Connect the demand connecting wires and relay connector R...

Page 13: ...02 CN100 CN105 Locally procured Power supply Indoor A E unit Connecting WARNING Do not connect the DRED mains cable to the terminal block of the outdoor unit Power supply and Indoor Outdoor connecting Improper installation may result in fire For the power supply of the DRED prepare exclusive power supply separated from that of the outdoor unit WARNING Connect the wire 4 wire with a round terminal ...

Page 14: ...he demand response event i e cooling or heating Wiring procedure 1 Securely fasten the demand connecting wires with the cord clamp located at the upper portion of the terminal block so that no external force is applied to the terminal The demand connecting wires having a relay connector RJ45 should be wired in such a manner as to prevent water intrusion into the relay connector 2 Bundle the demand...

Page 15: ...in units B C and E Trouble in units B D and E Trouble in units C D and E Trouble in units A B C and D Trouble in units A B C and E Trouble in units A B D and E Trouble in units A C D and E Trouble in units B C D and E Trouble in all units Service valve stays closed Gas Leak Inspection Refer to the Gas Leak Inspection on page 9 Test run 1 If you perform the test run in summer start running in the c...

Page 16: ...Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1116791001_EN indd 15 01 22 15 10 52 AM 1116791101_EN indd 15 1116791101_EN indd 15 2 3 58 BE 2 20 PM 2 3 58 BE 2 20 PM ...

Reviews: