background image

3

Outdoor Unit

Installation Manual

 

CAUTION

New refrigerant air conditioner installation 

THIS AIR CONDITIONER USES THE NEW HFC REFRIGERANT (R410A), WHICH DOES 
NOT DESTROY THE OZONE LAYER. 
R410A refrigerant is apt to be affected by impurities such as water, oxidizing membranes, 
and oils because the pressure of R410A refrigerant is approx. 1.6 times of refrigerant R22. 
As well as the adoption of this new refrigerant, refrigerating machine oil has also been 
changed. Therefore, during installation work, be sure that water, dust, former refrigerant, 
or refrigerating machine oil does not enter the refrigeration cycle of a new-refrigerant air 
conditioner. To avoid mixing refrigerant and refrigerating machine oil, the sizes of charging 
port connecting sections on the main unit are different from those for the conventional 
refrigerant, and different size tools are also required. For connecting pipes, use new and 
clean piping materials with high pressure withstand capabilities, designed for R410A only, 
and ensure that water or dust does not enter. Moreover, do not use any existing piping as its 
pressure withstand may be insufficient and may contain impurities. 

 

DANGER

•  The manufacturer shall not assume any liability for the damage caused by not observing 

the description of this manual. 

•  For use by qualified persons only. 
•  Means for disconnection from the supply having a contact separation of at least 3 mm in 

all poles must be incorporated in the fixed wiring. 

•  Turn off main power supply before attempting any electrical work. Make sure all power 

switches are off. Failure to do so may cause electric shock. 

•  Connect the connecting cables correctly. If the connecting cables are connected wrongly, 

electric parts may be damaged. 

•  Check the earth wire that it is not broken or disconnected before installation. 
•  Do not install near concentrations of combustible gas or gas vapors. Failure to follow this 

instruction can result in fire or explosion. 

•  To prevent overheating the indoor unit and causing a fire hazard, place the unit well away 

(more than 2 m) from heat sources such as radiators, heaters, furnace, stoves, etc. 

•  When moving the air conditioner for installing it in another place again, be very careful 

not to get the specified refrigerant (R410A) with any other gaseous body into the 
refrigeration cycle. If air or any other gas is mixed in the refrigerant, the gas pressure in 
the refrigeration cycle becomes abnormally high and it resultantly causes burst of the pipe 
and injuries on persons. 

•  In the event that the refrigerant gas leaks out of the pipe during the installation work, 

immediately let fresh air into the room. If the refrigerant gas is heated by fire or something 
else, It causes generation of poisonous gas. 

•  When installing or re-installing the air conditioner, do not inject air or other substances 

besides the designated refrigerant “R410A” into the refrigerating cycle.
If air or other substances are mixed, an abnormal pressure can occur in the refrigerating 
cycle, and this can cause an injury due to a pipe rupture. 

1116791101_EN.indd   3

1116791101_EN.indd   3

2/3/58 BE   2:20 PM

2/3/58 BE   2:20 PM

Summary of Contents for RAS-3M26S3AV-A

Page 1: ... TYPE Installation Manual Outdoor Unit Model name RAS 5M34S3AV A RAS 4M27S3AV A RAS 3M26S3AV A NOTE Descriptions about operations for the E unit in this manual are not applicable to RAS 4M27S3AV A Descriptions about operations for the D unit and the E unit in this manual are not applicable to RAS 3M26S3AV A 1116791101 1116791101_EN indd c1 1116791101_EN indd c1 2 3 58 BE 2 20 PM 2 3 58 BE 2 20 PM ...

Page 2: ...evice and Outdoor Unit 11 10 Test run 14 Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the outdoor unit For installation of the indoor unit refer to the Installation Manual attached to the indoor unit IMPORTANT NOTICE For details on how to install the indoor units refer to the installation manual accompanying t...

Page 3: ...ING It indicates that incorrect use of this unit may cause severe injury or death CAUTION It indicates that incorrect use of this unit may cause personal injury 2 or property damage 3 1 A severe injury refers to blindness injury burns hot or cold electrical shock bone fracture or poisoning that leaves after effects and requires hospitalization or extended out patient treatment 2 Personal injury me...

Page 4: ...wiring Turn off main power supply before attempting any electrical work Make sure all power switches are off Failure to do so may cause electric shock Connect the connecting cables correctly If the connecting cables are connected wrongly electric parts may be damaged Check the earth wire that it is not broken or disconnected before installation Do not install near concentrations of combustible gas...

Page 5: ...do so may cause the unit to fall water leakage fire or electrical shock After the installation work ensure that there is no leakage of refrigerant gas If the refrigerant gas leaks out of the pipe into the room and is heated by fire or something else from a fan heater stove or gas range it causes generation of poisonous gas Make sure the equipment is properly earthed Do not connect the earth wire t...

Page 6: ... be connected to the main power supply by means of a circuit breaker depending on the place where the unit is installed Failure to do so may cause electrical shock Follow the instructions in this installation manual to arrange the drain pipe for proper drainage from the unit Ensure that drained water is discharged Improper drainage can result in water leakage causing water damage to furniture Tigh...

Page 7: ...ditioner differs depending on the combination of the indoor units which are operated The information in this specifications table applies for the combinations with the catalogue For operation read the owner s manual packed with the indoor unit Equipment complying with IEC 61000 3 12 1 If the air conditioner is used in conditions other than the above the safety protection functions may be activated...

Page 8: ...ioner under low outside temperature conditions Outside temp 5 C or lower In COOL mode prepare a duct or wind shield so that it is not affected by the wind Necessary Space for Installation If you need to install the outdoor unit in a location where there are some obstructions or a wall secure sufficient space as shown in the figure below The cooling heating effect may be reduced by 10 Upper side vi...

Page 9: ... core Setting Pin using the charge hose NOTE If a control valve or charge valve is attached to the charge hose leak of R410A refrigerant can be avoided 2 Open the Handle Low of the gauge manifold valve fully then operate the vacuum pump Loosen the flare nut of the at the gas end a little to make sure that air is taken in then tighten the nut If you find air is not taken in make sure that the charg...

Page 10: ...rming Additional Installation of an Indoor Unit 1 Collect refrigerant from the outdoor unit 2 Turn off the circuit breaker 3 Perform additional installation referring to the procedure from Refrigerant Piping Connection on the previous page Pump down Operation Recovering refrigerant CAUTION Since the forcible running for collecting refrigerant stops automatically after 10 minutes finish collecting ...

Page 11: ... terminal numbers on the terminal block of each unit Incorrect connection may cause a failure 1 Detach the front panel from the outdoor unit 2 Remove the cord clamp 3 Connect the wires for the power source and each indoor unit Connect the connecting cable to the terminal as identified by the matching numbers on the terminal block of the indoor and the outdoor unit 4 Fix the wiring connections for ...

Page 12: ... connecting wire is incorrect electric parts may be damaged Ensure that all terminals are securely fixed so preventing any external forces having a negative effect on the terminals Do not connect the DRED mains cable to the terminal block of the outdoor unit Power supply and Indoor Outdoor connecting Improper installation may result in fire Connect the demand connecting wires and relay connector R...

Page 13: ...02 CN100 CN105 Locally procured Power supply Indoor A E unit Connecting WARNING Do not connect the DRED mains cable to the terminal block of the outdoor unit Power supply and Indoor Outdoor connecting Improper installation may result in fire For the power supply of the DRED prepare exclusive power supply separated from that of the outdoor unit WARNING Connect the wire 4 wire with a round terminal ...

Page 14: ...he demand response event i e cooling or heating Wiring procedure 1 Securely fasten the demand connecting wires with the cord clamp located at the upper portion of the terminal block so that no external force is applied to the terminal The demand connecting wires having a relay connector RJ45 should be wired in such a manner as to prevent water intrusion into the relay connector 2 Bundle the demand...

Page 15: ...in units B C and E Trouble in units B D and E Trouble in units C D and E Trouble in units A B C and D Trouble in units A B C and E Trouble in units A B D and E Trouble in units A C D and E Trouble in units B C D and E Trouble in all units Service valve stays closed Gas Leak Inspection Refer to the Gas Leak Inspection on page 9 Test run 1 If you perform the test run in summer start running in the c...

Page 16: ...Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1116791001_EN indd 15 01 22 15 10 52 AM 1116791101_EN indd 15 1116791101_EN indd 15 2 3 58 BE 2 20 PM 2 3 58 BE 2 20 PM ...

Reviews: