– 70 –
Item
18. Set temperature
correction
Operation flow and applicable data, etc.
Indoor Control P.C. Board (Factory Default)
Description
1. Purpose
When the difference between the set temp.
of the remote controller and the room temp.
is wide due to the installation condition, etc,
the set temp. is corrected.
(HEAT operation only)
2. Description
The set temp. received from the remote
controller is corrected.
The correct value from –2°C to +4°C is
changed by the jumper wire on P.C. board of
the indoor microcomputer.
L01
DB01
C03
T101
IC801
J804
J805
J806
J807
Jumper wire
J804
J805
J806
J807
In HEAT Operation
Jumper wire setup
J804
J805
×
×
×
¡
¡
×
¡
¡
HEAT
shift value
–2
+4
+2
0
←
At shipment
¡
: With Jumper wire
×
: Cut Jumper wire