– 62 –
Initial setting of “Cooling storage position”
Louver : Directs downward (23˚)*1
Dry operation
Louver angle
Horizontal
(0˚)
Cooling operation/AUTO (COOL)
Powerful
Initial setting of “Cooling storage position”
Louver : Directs downward (23˚)
∗
1
“Cooling storage position”
Louver : Directs downward (34˚)
SLEEP MODE operation
In case that the following temperature is obtained
during 12 minutes or 12 to 25 minutes from start
of heating operation: Room temperature (TA)
< Set temperature (Tsc) –3.0
In case that the following temperature is obtained
during 12 to 25 minutes from start of heating
operation: Room temperature (TA)
≥
Set temperature (Tsc) –3.0 or when 25 minutes
or more passed from start of heating operation.
“Heating storage position”
Louver : Directs downward (72˚)
“Cooling storage position”
Louver : Directs downward (23˚)
Heating operation/AUTO (HEAT)
Powerful
Initial setting of “Heating storage position”
Louver : Directs downward (72˚)
“Heating storage position”
Louver : Directs downward (58˚)
Item
9. Louver control
1) Louver
position
Operation flow and applicable data, etc.
This function controls the air direction of the indoor unit.
Description
3) Swing
3) Louver position in dry operation
• The position is automatically controlled according to the operation mode (COOL/HEAT).
• The set louver position is stored in memory by the microcomputer, and the louver returns to the
stored position when the next operation is performed. (Cooling/heating memory position)
The angle of the louver is indicated as the horizontal angle is 0°.
When the louver closes fully, it directs approx. 10° upward.
1) Louver position in cooling operation
2) Air direction
adjustment
1) When pushing [SWING] button during operation, the louver starts swinging.
2) Each time you push the SWING button, you can change the swing mode.
(Vertical swing
→
Horizontal swing
→
Vertical and Horizontal swing
→
Stop swinging)
• Swing operation is performed in width 35° with the stop position as the centre.
• If the stop position exceeds either upper or lower limit position, swing operation is performed in
width 35° from the limit which the stop position exceeded.
Horizontal
blowing
Inclined
blowing
Inclined
blowing
Inclined
blowing
Inclined
blowing
Blowing
downward
∗
1 When the indoor humidity is high (Hu sensor valve)
≥
70%), the compressor speed is 23
rps or more and the position of the louver is less than 29°, the louver moves to 29° to
prevent the air outlet from dew drop. And the louver can’t move to less than 29°.
When the indoor humidity becomes low or the compressor speed becomes less than 23
rps, the louver returns to the storage position.
2) Louver position in heating operation
• The louver position can be arbitrarily set up by pushing [FIX] button.