Q7 ASD Installation and Operation Manual
71
Jump Frequency 2
Program
⇒
Special Controls
⇒
Jump Frequency 2
This parameter establishes the Jump Frequency 2 setting.
Once set up and enabled, it is on in all control modes.
See the
parameter for further information on this setting.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq.
Units — Hz
Jump Frequency 3
Program
⇒
Special Controls
⇒
Jump Frequency 3
This parameter establishes the Jump Frequency 3 setting.
Once set up and enabled, it is on in all control modes.
See the
parameter for further information on this setting.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq.
Units — Hz
LCD Contrast
Program
⇒
Special Controls
⇒
LCD Contrast
Press the Up/Down Arrow keys to increase or decrease the contrast of the LCD
screen.
Parameter Type — Numerical
Factory Default — 4
Changeable During Run — Yes
Minimum — 0
Maximum — 7
LED Option Override Multiplication Gain
Program
⇒
Protection
⇒
LED Opt Override
This feature adjusts the gain of the external adjustment of the output frequency
(using RR, RX, etc.) while using the LED keypad.
Note: The LED Keypad is under development and is unavailable at
the time of the release of this manual.
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — -100.00
Maximum — 100.00
Lock-on Rate
Program
⇒
Protection
⇒
Lock-on Rate
After a momentary power outage, the ASD may have to startup into a spinning
motor. The Lock-on Rate is the difference between the time that the RPM of
the motor is determined by the ASD and the time that the ASD outputs a drive
signal to the motor.
The Speed Search parameter must be enabled to use this feature.
Parameter Type — Numerical
Factory Default — 1.00
Changeable During Run — No
Minimum — 0.50
Maximum — 2.50
Units — Seconds