106
Q7 ASD Installation and Operation Manual
RX Speed Frequency #2
Program
⇒
Freq Settings
⇒
RX Speed Freq #2
This parameter is used to set the direction, gain, and bias of the RX input
terminal when the RX terminal is used as the control input while operating in
the Speed Control mode.
for further information on this setting.
and is the frequency that is
associated with the setting of
Speed Control mode.
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — Yes
Minimum — -Max. Freq.
Maximum — +Max. Freq.
Units — Hz
RX Speed Reference #1
Program
⇒
Freq Settings
⇒
RX Speed Ref #1
This parameter is used to set the direction, gain, and bias of the RX input
terminal when the RX terminal is used as the control input while operating in
the Speed Control or the Torque Control mode.
for further information on this setting when used
for Speed control.
for further information on this setting when used
for Torque control.
This parameter sets the RX input level that is associated with
when operating in the Speed control mode or is associated with
when operating in the Torque control mode.
This value is entered as -100 to +100% of the -10 to +10 VDC RX input signal
range.
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — -100.0
Maximum — 100.0
Units — %
RX Speed Reference #2
Program
⇒
Freq Settings
⇒
RX Speed Ref #2
This parameter is used to set the direction, gain, and bias of the RX input
terminal when the RX terminal is used as the control input while operating in
the Speed Control or the Torque Control mode.
for further information on this setting when used
for Speed control.
for further information on this setting when used
for Torque control.
This parameter sets the RX input level that is associated with
when operating in the Speed control mode or is associated with
when operating in the Torque control mode.
This value is entered as -100 to +100% of the -10 to +10 VDC RX input signal
range.
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Yes
Minimum — -100.0
Maximum — 100.0
Units — %