Q7 ASD Installation and Operation Manual
19
Control Terminal Strip
I/O and Control
The Q7 ASD can be controlled by several input types and combinations thereof, as well as operate
within a wide range of output frequency and voltage levels. This section describes the ASD control
methods and supported I/O functions.
The Control Terminal Strip PCB (P/N 48570) supports discrete and analog I/O functions.
The Control Terminal Strip is shown in
and lists the names, the default
settings, and the descriptions of the input and output terminals.
shows the basic connection diagram for the Q7 system.
Table 3. Control Terminal Strip default assignment terminal names and functions.
Terminal
Name
Input/Output
Terminal Function
(default setting if programmable)
Circuit Config.
ST
Discrete Input
Standby (jumper to CC to operate the unit) — Multifunctional
programmable discrete input (see
for further
information on this terminal).
RES
Discrete Input
Reset — Multifunctional programmable discrete input.
F
Discrete Input
Forward — Multifunctional programmable discrete input.
R
Discrete Input
Reverse — Multifunctional programmable discrete input.
S1
Discrete Input
Fire Speed
— Multifunctional programmable discrete input.
S2
Discrete Input
Preset Speed 2 — Multifunctional programmable discrete input.
S3
Discrete Input
Damper Fdbk — Multifunctional programmable discrete input (connect
to CC to operate the unit).
S4
Discrete Input
Emergency Off — Multifunctional programmable discrete input.
RR
Analog Input
RR — Multifunction programmable analog input
(0.0 to 10 volt input — 0 to 80 Hz output). Reference CC.
RX
Analog Input
RX — Multifunctional programmable analog input
(-10 to +10 VDC input — -80 to +80 Hz output). Reference CC.
II
Analog Input
II — Multifunctional programmable analog input (4 [0] to 20 mADC
input — 0 to 80 Hz output) (see
for the location of
the II terminal). Reference CC.
VI
Analog Input
VI — Multifunctional programmable analog input
(0 to 10 VDC input — 0 to 80 Hz output). Reference CC.
P24
DC Output
24 VDC @ 50 mA output.
PP
DC Output
PP — 10.0 VDC voltage source for the external potentiometer.
OUT1
Discrete Output
Damper Command — Damper Command — Multifunctional
programmable output that is used to open/close the 120 VAC damper
motor power circuit when the motor is ASD-driven.
OUT2
Discrete Output Reach Frequency — Multifunctional programmable discrete output.
FP
Output
Frequency Pulse — an output pulse train that has a frequency which is
based on the output frequency of the ASD.
AM
Output
Produces an output current that is proportional to the magnitude of the
function assigned to this terminal (see
).
FM
Output
FLC
Output
Fault relay (common).
FLB
Output
Fault relay (N.C.).
FLA
Output
Fault relay (N.O.).
CC
—
Control common (Do Not connect to Earth Gnd).
Discrete Input Terminals
⇒
On = connected to CC.
Analog Input terminals reference CC.