– 9 –
1-2. Floor console recessed Type
Model name
MML-
AP0074BH2UL
AP0094BH2UL
AP0124BH2UL
AP0154BH2UL
Cooling capacity
kBtu/h
7.5
9.5
12.0
15.4
Heating Capacity
kBtu/h
8.5
10.5
13.5
17.0
Electrical
Power supply
230V(208V/230V) 1phase 60Hz
charastaristics
Power consumption
208V
kW
0.047
0.047
0.047
0.095
230V
kW
0.056
0.056
0.056
0.114
Appearance
Zinc hot dipping steel plate
Height
In
23.6
23.6
23.6
23.6
Dimension
Unit
Width
In
29.3
29.3
29.3
41.1
Depth
In
8.7
8.7
8.7
8.7
Height
In
26.9
26.9
26.9
26.9
Packing
Width
In
31.9
31.9
31.9
43.7
Depth
In
10.8
10.8
10.8
10.8
Total weight
Unit
lbs
50.7
50.7
50.7
68.3
Packing
lbs
57.3
57.3
57.3
75.0
Heat exchanger
Finned tube
Fan
Centrifugal fan
Fan unit
Standard air flow(High/Mid/Low)
cfm
270 / 240 / 180
270 / 240 / 180
270 / 240 / 180
440 / 350 / 290
Motor
W
19
19
19
70
Connecting pipe
Gas side
In
3/8"
3/8"
3/8"
1/2"
Liquid side
In
1/4"
1/4"
1/4"
1/4"
Drain port (Nominal dia. mm)
20(Polyvinyl chloride tube)
Sound puressure level (High/Mid./Low(*1)
208V
dB(A)
40 / 36 / 33
40 / 36 / 33
40 / 36 / 33
40 / 36 / 33
230V
dB(A)
42 / 39 / 36
42 / 39 / 36
42 / 39 / 36
43 / 39 / 36
Model name
MML-
AP0184BH2UL
AP0244BH2UL
Cooling capacity
kBtu/h
18.0
24.0
Heating Capacity
kBtu/h
20.0
27.0
Electrical
Power supply
230V(208V/230V) 1phase 60Hz
charastaristics
Power consumption
208V
kW
0.095
0.104
230V
kW
0.114
0.120
Appearance
Zinc hot dipping steel plate
Height
In
23.6
23.6
Dimension
Unit
Width
In
41.1
41.1
Depth
In
8.7
8.7
Height
In
26.9
26.9
Packing
Width
In
43.7
43.7
Depth
In
10.8
10.8
Total weight
Unit
lbs
68.3
68.3
Packing
lbs
75.0
75.0
Heat exchanger
Finned tube
Fan
Centrifugal fan
Fan unit
Standard air flow(High/Mid/Low)
cfm
440 / 350 / 290
560 / 470 / 380
Motor
W
70
70
Connecting pipe
Gas side
In
1/2"
5/8"
Liquid side
In
1/4"
3/8"
Drain port (Nominal dia. mm)
20(Polyvinyl chloride tube)
Sound puressure level (High/Mid./Low(*1)
208V
dB(A)
40 / 36 / 33
47 / 42 / 35
230V
dB(A)
43 / 39 / 36
49 / 44 / 37
Note
(*1) The actual value s in an external operating environment are generally higher than the indicated values
due to the contribution from ambient noise.
All manuals and user guides at all-guides.com