7. APPLIED CONTROL
7-1. Setup of Selecting Function in Indoor Unit
(Be Sure to Execute Setup by a Wired Remote Controller)
<Procedure>
Execute the setup operation while the unit stops.
1
Push
SET
,
CL
, and
TEST
buttons simultaneously for 4 seconds or more.
The firstly displayed unit No. indicates the header indoor unit address in the group control.
In this time, the fan of the selected indoor unit is turned on.
2
Every pushing
UNIT LOUVER
button, the indoor unit numbers in the group control are successively
displayed. In this time, the fan of the selected indoor unit only is turned on.
3
Specify the CODE No. (DN) using the setup temperature
and
buttons.
4
Select the setup data using the timer time
and
buttons.
(When selecting the CODE No. (DN) to “
33
33
33
33
33
”, change the temperature indication of the unit
from “ °C ” to “ °F ” on the remote controller.)
5
Push
SET
button. (OK if display goes on.)
• To change the selected indoor unit, return to procedure
2
.
• To change the item to be set up, return to procedure
3
.
6
Pushing
TEST
button returns the status to normal stop status.