Procedure
2
Each time you push
button, indoor unit
numbers in the control group change cyclically.
Select the indoor unit you want to change settings
for.
The fan of the selected unit runs and the louvers
start swinging. You can confirm the indoor unit for
which you want to change settings.
Procedure
3
Using “TEMP.”
/
buttons, specify CODE
No..[
].
Procedure
4
Using timer “TIME”
/
buttons, select SET
DATA [
].
Procedure
5
Push
button. When the display changes from
flashing to lit, the setup is completed.
To change settings of another indoor unit, repeat
from Procedure
2
.
To change other settings of the selected indoor
unit, repeat from Procedure
3
.
Use
button to clear the settings.
To make settings after
button was pushed,
repeat from Procedure
2
.
Procedure
6
When settings have been completed, push
button to determine the settings.
When
button is pushed, “SETTING” flashes and
then the display content disappears and the air
conditioner enters the normal stop mode.
(While “SETTING” is flashing, no operation of the
remote controller is accepted.)
Change of lighting time of filter
sign
According to the installation condition, the lighting
time of the filter sign (Notification of filter cleaning)
can be changed.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
For the CODE No.. in Procedure
3
, specify [01].
For the [SET DATA] in Procedure
4
, select the
SET DATA of filter sign lighting time from the
following table.
To secure better effect of heating
When it is difficult to obtain satisfactory heating due
to installation place of the indoor unit or structure of
the room, the detection temperature of heating can
be raised. Also use a circulator, etc. to circulate
heat air near the ceiling.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
For the CODE No.. in Procedure
3
, specify [06].
For the SET DATA in Procedure
4
, select the
SET DATA of shift value of detection
temperature to be set up from the table below.
SET DATA
Filter sign lighting time
0000
None
0001
150H (Factory setting)
0002
2500H
0003
5000H
0004
10000H
SET DATA
Detection temp shift value
0000
No shift
0001
+1°C
0002
+2°C
0003
+3°C (Factory setting)
0004
+4°C
0005
+5°C
0006
+6°C
1111058602_EN.indd 28
11/24/16 11:41 AM
SET DATA
Detection temp shift value
0000
No shift
0001
+1°C
0002
+2°C (Factory setting)
0003
+3°C
0004
+4°C
0005
+5°C
0006
+6°C
FILE NO. SVM-17045
- 95 -