91
–
No.
⑨
⑩
Part name
Procedure
Remarks
1. Detachment
1) Recover the refrigerant gas and then remove the
refrigerant pipe of the indoor unit.
2) Perform 1 of
⑧
.
3) Perform 1 of
⑨
.
4) Remove the screws (M8 x 20, 5 pcs) and remove
the right side panel.
5) Remove the screws (M8 x 20, 4 pcs) and remove
the evaporator partition (back).
6) While holding the heat exchanger, remove the fixing
screws (M8 x 20, 5 pcs) of the fixing end plate (UP)
and evaporator partition (DOWN) and then take out
the heat exchanger slowly.
Heat
exchanger
Sensor
TC1,TC2,TCJ
Fixing screws
Right side panel
Evaporator partition (back)
Fixing screws
1. Detachment
1) Perform 1 of
①
to open the electrical parts box cover.
2) Loosen the fixing screws of the inspection cover and
open the inspection cover.
3) Remove the connectors of the wires of TC1 sensor ,
TC2 sensor and TCJ sensor from the
control
P.C. board.
CN100 : TC1 sensor (3P: Brown)
CN101 : TC2 sensor (2P: Black)
CN102 : TCJ sensor (2P
:
Red)
2. Attachment
1) Attach the TC1 sensor , TC2 sensor and TCJ sensor to
the original position.
2) Wire the wires of TC1 sensor, TC2 sensor, and TCJ
sensor as before.
3) Attach the left side panel as before.
Heat exchanger
Screw
Inspection cover
Control P.C.board
MCC-1643
TCJ sensor
TC2 sensor
TC1 sensor
AMP Air Conditioning
www.ampair.co.uk | [email protected]