92
–
No.
⑩
⑪
⑫
Part name
Procedure
Remarks
2. Attachment
1) Attach the heat exchanger to the original position,
attach the fixing end plate (UP) and evaporator
partition (
Down
) as before.
2) Attach the evaporator partition (back) as before.
3) Wire the wires of TC1 sensor, TC2 sensor, and TCJ
sensor as before.
4) Attach the right side panel and left side panel as before.
5) Perform 2 of
⑧
.
6) Attach the bottom base as before.
Sensor TA
Reactor
Evaporator partition (DN)
Fixing end plate (UP)
Fixing screws
NOTE
After assembling, check if that there is no abnormal sound,
vibration, or puncture.
Check the exchange point when you have a problem.
Heat
exchanger
Electric al parts
box
TA sensor holder
TA sensor
CN104
1. Detachment
1) Perform 1 of
①
and 1 of
⑥
.
2) Remove the connector of the wires of TA sensor from
the control P.C. board.
3) Pinch the lock of the TA sensor holder from the outside
of the electrical parts box and push it into the inside
of the electrical parts box.
1)
2. Attachment
Attach the TA sensor to the original position.
2) Wire the wires of TA sensor in the holder as before.
3) Attach the electronical parts box as before.
1. Detachment
1) Perform 1 of
①
and 1 of
⑥
.
2) Remove the connector of the wires of the reactor
from the fan control P.C. board.
3) Remove the fixing screws fixing the reactor cover.
Slide the reactor cover to the arrow direction and
remove.
3) Remove the fixing screws fixing the reactor.
Remove the reactor from the reactor cover.
2. Attachment
1) Attach the reactor to the reactor cover.
2) Attach the reactor cover as before.
3) Wire the wires of the reactor in the holder as before.
Fixing screws
Fixing screws
Reactor
Reactor cover
CN511
CN510
Reactor assembly
AMP Air Conditioning