Function CODE No. (DN Code) table (includes all functions needed to perform applied control on site)
DN
Item
Description
At shipment
01
Filter display delay timer 0000: None
0002: 2500H
0004: 10000H
0001: 150H
0003: 5000H
According to type
02
Dirty state of filter
0000: Standard
0001: High degree of dirt (Half of standard time)
0000: Standard
1E
Temp difference of
[AUTO] mode selection
COOL
→
HEAT,
HEAT
→
COOL
0000: 0 deg
to
0010: 10 deg
(For setup temperature, reversal of COOL / HEAT by } (Data value) / 2)
0003: 3 deg
(Ts ±1.5)
06
Specific indoor unit
priority
Heating temp shift
0000: No shift
0002: +2
&
0001: +1
&
0010: +10
C
(Up to +6 recommended)
to
2E
HA terminal (CN61)
select
0000: Usual
0002: Fire alarm input
0001: Leaving-ON prevention control 0000: Usual
(HA terminal)
2A
Selection of option / error
input (CN70)
0000: Filter input
0002: None
0001: Alarm input (Air washer, etc.) 0002: None
28
Automatic restart of
power failure
0000: None
0001: Restart
0000: None
14
Group address
0000: Individual
0002: Follower unit of group
0001: Header unit of group
0099: Unfixed
11
Indoor unit capacity
0000: Unfixed
0001 to 0034
According to capacity
type
12
0001: No.1 unit
to
0099: Unfixed
32 TA sensor selection
0000: Body TA sensor
0001: Available
0001: Remote controller sensor
0000: Unavailable
0000: Body TA sensor
33 Temperature unit select 0000:
o
&
(at factory shipment)
0001:
F
0000:
C
31 Ventilating fan control
0000: Unavailable
13
Line address
Indoor unit address
0001: No.1 unit
0030: No.30 unit
0064: No.64 unit
to
0099: Unfixed
10
Type
&RQFHDOHG'XFW+LJK6WDWLF3UHVVXUH7\SH
* refer to
QH[W
page Type CODE No. [10]
Depending on model
type
0F
Cooling only
0000: Heat pump
0001: Cooling only (No display of [AUTO] [HEAT])
0000: Heat pump
0d
Existence of [AUTO]
mode
0000: Provided
0001: Not provided (Automatic selection from connected outdoor unit)
0002: +2
C
(Floor type 0000: 0
C)
0001: Not provided
04
0000: No priority
0001: Priority
0000: No priority
03
Central control address 0001: No.1 unit
0099: Unfixed
0064: No.64 unit
to
0099: Unfixed
Static pressure selection
0000: Standard
0006
The list abpve is when SW501-1 and SW501-2 is OFF.
Pa
0005
1
Pa
0004
Pa
0003
50 Pa
0002
Pa
0001
Pa
0000
Pa
(Factory
default)
Set data
External static
pressure
60
Timer setting
(wired remote controller)
0000: Available (can be performed) 0001: Unavailable
(cannot be performed)
0000: Available
92
External interlock
release condition
0000: Operation stopped
0001: Release signal received
0000: Operation
stopped
D0
Whether the power
saving mode can be set
by the remote controller
0000: Invalid
0001: Valid
0001: Valid
5d
77 Dual set point
0000:
Unavailable
000
2
:
Available
0000:
Unavailable
F6 Presence of Application
control kit
0000:
None
000
1
:
Connect
0000:
None
Fd Priority operation mode
(FS unit)
0000:
Heating
000
1
:
Cooling
0000:
Heating
00
99
:
Unfixed
0099: Unfixed
FE FS unit address
000
1
:
No.1 unit to 0064 : No.64 unit
AMP Air Conditioning