–
48
–
Check code clearing function
How to clear the check code using the wired remote controller
Clearing an check code of the outdoor unit
Clear the currently detected outdoor unit for each refrigerant line to which the indoor
unit controlled by the remote controller is connected. (The indoor unit check code is
not cleared.) Use the service monitoring function of the remote controller.
1
Push and hold the
CL
, and
for 4 seconds or longer to enter the service monitoring
mode.
2
Push the
TEMP.
button to set CODE No. to “FF”.
3
The display in A of the following figure counts down as follows at 5-second intervals:
“
0005
0005
0005
0005
0005
”
→
→
→
→
→
“
0004
0004
0004
0004
0004
”
→
→
→
→
→
“
0003
0003
0003
0003
0003
”
→
→
→
→
→
“
0002
0002
0002
0002
0002
”
→
→
→
→
→
“
0001
0001
0001
0001
0001
”
→
→
→
→
→
“
0000
0000
0000
0000
0000
”.
The
check code
is cleared when “
0000
0000
0000
0000
0000
” appears.
However, the display counts down from “
0005
0005
0005
0005
0005
” again.
4
Push the
to return the display to normal.
4
3
2
1
SET
TIME
TIMER SET
TEST
FILTER
RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
Clearing an check code of the indoor unit
Push the
ON / OFF
button on the remote controller.
(Only the check code of the indoor unit controlled by the remote controller will be
cleared.)
AMP Air Conditioning
www.ampair.co.uk | [email protected]