– 13 –
1. SPECIFICATIONS
Concealed Duct High Static Pressure Type
(50/60Hz)
Model name
MMD-
AP0726HP-E (TR)
AP0966HP-E (TR)
Cooling capacity …Note 1
(kW)
22.4
28.0
Heating capacity …Note 1
(kW)
25.0
31.5
Electrical
Power supply
1 phase 50Hz 230V(220V-240V) / 1 phase 60Hz 220V
characteristics
Running current (50/60Hz)
(A)
2.80
/
2.93
3.75
/
3.92
(factory setting)
Power consumption
(W)
540
/
540
790
/
790
Starting current (50/60Hz)
(A)
7.80
/
8.15
7.80
/
8.15
Appearance
Zinc hot dipping steel plate
Dimension
Height
(mm)
448
Width
(mm)
1400
Depth
(mm)
900
Total weight
(kg)
97
Heat exchanger
Finned tube
Soundproof / Heat-insulating
material
Polyethylene
foam
Fan unit
Fan
Centrifugal fan
(m3/h)
3,800
4,800
Standard air flow
(Med./Low)
(3,200/2,500)
(4,200/3,500)
Motor output
(W)
250
External static pressure (factory setting)
(Pa)
150
External static pressure range
(Pa)
50-83-117-150-183-217-250 (7 steps)
Controller
Remote controller
Air filter
Sold separately (TCB-LK2801DP-E)
Drain pump
Sold separately (TCB-DP40DPE)
Connecting
Gas side
(mm)
Φ22.2
pipe
Liquid side
(mm)
Φ12.7
Drain port
(mm)
25 (Polyvinyl chloride tube)
(dB(A))
44 / 40 / 36
46 / 42 / 38
Sound power level (High/Med./Low)
(dB(A))
79 / 75 / 71
81 / 77 / 73
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based
on the reference piping.
The reference piping consists of 5m of main piping and 2.5m of branch piping connected with 0 meter height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated valves due to the
effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27℃ DB/19℃ WB, Outdoor air temperature 35℃ DB
Heating : Indoor air temperature 20℃ DB, Outdoor air temperature 7℃ DB/6℃ WB
Sound pressure level (High/Med./Low) …Note 2
(factory setting)
AMP Air Conditioning