81
–
Check code
Main remote
controller
L03
L04
L05
L06
L07
L08
L09
L10
L20
L28
L29
L30
—
Outdoor 7-segment display
Check code
—
L04
—
L06
—
L08
—
L10
—
L28
L29
L30
L31
Sub-code
—
—
—
No. of indoor units with priority
—
—
—
—
—
—
01: IPDU1 error
02: IPDU2 error
03: IPDU1, 2 errors
04: Fan IPDU error
05: IPDU1 + Fan IPDU error
06: IPDU2 + Fan IPDU error
07: All IPDU error or
communication error between
IPDU and I/F P.C. board,
or outdoor I/F P.C. board error
Detected indoor address
—
Detected
position
Indoor
I/F
I/F
I/F
Indoor
Indoor
Indoor
I/F
Indoor
I/F
I/F
Indoor
I/F
Check code name
Duplicated indoor center units
Duplicated outdoor line address
Duplicated indoor units with priority
(Displayed on indoor unit with priority)
Duplicated indoor units with priority
(Displayed on the unit other than
indoor unit with priority)
Group line in individual indoor unit.
Indoor group / address unset
Indoor capacity unset
Outdoor capacity unset
Duplicated central control addresses
Quantity over of connected outdoor
units
IPDU quantity error
Interlock in indoor unit from outside
Extended IC (Integrated Circuit) error
Status
Corresponding
unit only stops.
All stop
All stop
All stop
Corresponding
unit only stops.
Corresponding
unit only stops.
Corresponding
unit only stops.
All stop
All stop
All stop
All stop
Corresponding
unit only stops.
Operation
continues.
Error detection condition
There are multiple center units in
a group.
Line address setup is duplicated
against the outdoor unit in
different refrigerant pipe system.
Indoor units with priority were
duplicated.
Indoor units with priority were
duplicated.
At least one indoor unit
connected to a group existed in
the individual indoor units.
Address was not yet set up.
Indoor unit capacity was unset.
On the I/F P.C. board for service,
jumper line was not cut
according to the model.
Duplicated central control
addresses
There were more than four
outdoor units.
No. of IPDU units detected when
power was turned on were less.
• Outside error input terminal
Detected signal to (CN80) for
more 1 minute
P.C. board (I/F) parts error
Check item (position)
• Check indoor address.
• Check the change of remote controller connection
(Group/individual) after indoor address setup.
• Check line address.
• Check display of indoor unit with priority.
• Check display of indoor unit with priority and outdoor
unit.
• Check indoor address.
• Check indoor address.
Note)
After installation, this code is displayed when the power is
firstly turned on.
Set up indoor capacity. (DN=11)
Check model setup on outdoor I/F P.C. board A’ssy for
service.
• Check central control address.
• Check No. of connected outdoor units.
(Max. 4 units per 1 system)
• Check communication line between outdoor units.
• Check outdoor P.C. board (I/F) error.
• Check model setup for outdoor I/F service P.C. board.
• Check connection of UART communication connector.
• Check IPDU, fan IPDU, and I/F P.C. board error.
Note)
UART: Universal Asynchronous Receiver Transmitter
n
Outside device is connected to connector (CN80):
1) Check outside device error.
2) Check indoor P.C. board error.
n
Outside device is not connected to connector (CN80):
1) Check indoor P.C. board error.
Check indoor (I/F) P.C. board.