– 60 –
NOTE) The Test run operation returns to the normal operation after 60 minutes elapsed.
1, 5
3
2, 4
ON / OFF
FAN
TEMP.
SWING/FIX
TIME
MODE
VENT
UNIT
SET
CL
FILTER
RESET TEST
TIMER SET
<Wired remote controller>
Procedure
1
2
3
4
5
Operation contents
When pushing [CHECK] button for 4 seconds or more,
[TEST
TEST
] is displayed on the display part and the mode
enters in Test operation mode.
Push [ON / OFF
ON / OFF
] button.
Using [MODE] button, select an operation mode,
[COOL] or [HEAT].
• Do not use other than [COOL] / [HEAT] mode.
• Temperature cannot be adjusted during test operation.
• Detection of error is performed as usual.
When test operation finished, push [ON / OFF
ON / OFF
] button to stop operation.
(The same display as Procedure
1
is displayed.)
Push [CHECK] button to release the Test operation mode.
([TEST
TEST
] display on the display part disappears and
the status becomes normal stop status.)
TEST
10-3. Function during Test Operation
n
Cooling / Heating Test Operation Check
The test operation for cooling/heating operation can be performed from either indoor remote controller or
outdoor interface P.C. board.
1. Start / Stop operation of test operation
• Test operation from indoor remote controller