– 27 –
Installation of indoor unit
1. Install temporarily the indoor unit.
• Attach the hanging bracket to the hanging bolt.
Be sure to fix the hanging bracket from both up
and down sides of the hanging bracket by using
the nuts (M10 procured locally) and the washer.
2. Using nut, adjust height of the main unit.
3. Check the main unit is horizontally installed.
• Attach canvas ducts (procured locally) to the air
inlet and the air outlet so that vibration of the
main unit does not travel to the duct or ceiling.
Attach also acoustic-absorption material to the
inner liner of the duct and the vibration-proof
rubber to the hanging bolt.
Main unit
Hanging bolt
Nut (Upper side)
Washer (Upper side)
Thermal insulator
(Hanging bracket main unit)
Washer (Lower side)
Nuts (Lower side)
Using a level vial or vinyl hose, check whether the indoor unit is hung horizontally or not.
Thermal insulation
Front view
Side view
Install the main unit within 5mm while lowering
the drain pipe connecting port side slightly.
Install both air inlet and air supply port sides
within ±5mm.
Vinyl hose
Water pouring
Level vial
Level vial
0 to 5mm
±5mm
CAUTION
Make sure that the unit is hanging level.
If it is hung horizontally, the drain pan may overflow. Install the unit within the dimensions indicated below.
4