– 45 –
REQUIREMENT
When the external static pressure was changed, enter the changed static pressure value in the identification
plate of the unit.
Wire connection change for fan motor
The motor wires for the fan have been connected to F
2
at shipment from the factory.
Change the wire connection if change of the external static pressure is required due to the duct resistance.
<MMD-AP0481HFE>
Terminal block No.
F1 (Low static pressure tap)
F2 (Intermediate static pressure tap)
F3 (High static pressure tap)
Fan motor wiring
Blue (50 / 60Hz)
Orange (50 / 60Hz)
Black (50 / 60Hz)
Remarks
—
At shipment from factory
—
Lead wire for changing the external static pressure
When changing the external static pressure is
necessary, change connection of this lead wire.
Electric parts box
4P terminal block
2P terminal block
Control
P.C. board
Fan motor
Blue
Blac
k
Orange (at shipment of factory)
F1
F2
F3
F4
Or
ange
FM
Fan motor
Blue
Blac
k
Orange (at shipment of factory)
F1
F2
F3
F4
Or
ange
FM
Lead wire for changing the external static pressure
When changing the external static pressure is
necessary, change connection of this lead wire.
Electric parts box
4P terminal block
2P terminal block
Control
P.C. board
Fan motor
Blue
Blac
k
Orange (at shipment of factory)
F1
F2
F3
F4
Or
ange
FM
<MMD-AP0721HFE>
<MMD-AP0961HFE>
10
FAN CHARACTERISTICS