41
6 F 2 S 0 8 7 7
4.7.3 Group setting change
G1IF4 converts four IEC103 signals for group setting indication into Group 1 to 4 for
IEC61850. The action of changing a setting group takes about 3 seconds to complete. Therefore,
following a group setting change command, it is recommended that the SAS should wait at least
3 seconds before requesting confirmation of the setting group.
When changing Group 1 to 2:
IEC61850
ActSG
1→ 2
Mapping
1
2
3
4
IEC-103
Issue Group
change 2
1
2
3
4
Grp2 : On
Grp1 : Off
ActSG
2
W
R
4.7.4 DEADBAND setting of measurement value
In accordance with IEC103 measurands are transmitted every second, while in IEC61850 only
changes in value are reported. In order to avoid repeated transmissions due to insignificant
changes in value, a DEADBAND setting is provided. Data on the IEC61850 side is updated only
when the measurement value reported by IEC103 has changed by more than DEADBAND
setting.
IEC-103
Measurement value
4096/(Rated value
1.2)
or
4096/(Rated value
2.4)
Mapping
Comparing the previous value
Newest measurement value
Previous value
(4096/1.2×DEADBAND setting %)
or
Newest measurement value
Previous value
(4096/1.2×DEADBAND setting %)
IEC61850
Update
Previous value
Previous value
(4096/1.2×DEADBAND setting %)
Previous value
(4096/1.2×DEADBAND setting %)
Update
Update
Summary of Contents for G1IF4
Page 29: ... 28 6 F 2 S 0 8 7 7 4 2 9 Active group Active group Group 1 fixed ...
Page 34: ... 33 6 F 2 S 0 8 7 7 IFU side setting ...
Page 35: ... 34 6 F 2 S 0 8 7 7 And then check the connecting status by RSM100 ...
Page 48: ... 47 6 F 2 S 0 8 7 7 Appendix A External Connections ...
Page 50: ... 49 6 F 2 S 0 8 7 7 Appendix B Outline Diagram ...
Page 52: ... 51 6 F 2 S 0 8 7 7 Appendix C Signal List ...
Page 103: ... 102 6 F 2 S 0 8 7 7 ...
Page 104: ... 103 6 F 2 S 0 8 7 7 Appendix D Setting Sheet 1 Relay Unit Identification 2 Default setting ...
Page 118: ... 117 6 F 2 S 0 8 7 7 Appendix E Return Repair Form ...
Page 121: ... 120 6 F 2 S 0 8 7 7 ...
Page 122: ... 121 6 F 2 S 0 8 7 7 Appendix F Technical Data ...
Page 125: ... 124 6 F 2 S 0 8 7 7 ...
Page 126: ... 125 6 F 2 S 0 8 7 7 Appendix G Ordering ...
Page 129: ......