40
6 F 2 S 0 8 7 7
4.7 Modification of IEC103 Data
4.7.1 Autoreclose status
Autoreclose status values 1, 2 and 3 are created from three signals of IEC60870-5-103.
Though IEC60870-5-103 basically reports only 0/1 (off/on) information, IEC61850 needs to
convert the autoreclose status into the status values 1 to 3.
Therefore, G1IF4 provides the following signal processing function for the three signals of
IEC60870-5-103.
IEC103 Information
(Autoreclose Success)
IEC103 Information
(Autoreclose In-progress)
IEC103 Information
(Autoreclose Ready)
Setting for
Autoreclose
Signal Selection
ARCx.y.INF
Status Table No501
Autoreclose Status Value→3
Autoreclose Status Value→2
Autoreclose Status Value→1
The three signals cannot be output in some relay types. In this case, only the signal “Autoreclose
Success” is available.
Condition:
ARC
.S.INF = INF number specified.
ARC
.I.INF and ARC
.R.INF = INF number not specified.
If above condition is satisfied, it functions as follows.
Autoreclose success “on”
Autoreclose status value
“3”
Autoreclose success “off”
Autoreclose status value
“1”
4.7.2 Fault location value (km
Z, Z
km conversion)
Though IEC103 reports the fault location result in an impedance value or in a distance (km), the
IEC61850 requires that both results are output simultaneously.
G1IF4 functions as follows.
IEC-103 Table
Measurement Table No1
The value converted to impedance
regarding the IEC103 information as
distance (km).
Measurement Table No21
The value converted to distance (km)
regarding the IEC103 information as
impedance.
FLrate setting
FLrate setting
IEC61850
Change by Mapping
IEC-103
Information
(unmodified)
Summary of Contents for G1IF4
Page 29: ... 28 6 F 2 S 0 8 7 7 4 2 9 Active group Active group Group 1 fixed ...
Page 34: ... 33 6 F 2 S 0 8 7 7 IFU side setting ...
Page 35: ... 34 6 F 2 S 0 8 7 7 And then check the connecting status by RSM100 ...
Page 48: ... 47 6 F 2 S 0 8 7 7 Appendix A External Connections ...
Page 50: ... 49 6 F 2 S 0 8 7 7 Appendix B Outline Diagram ...
Page 52: ... 51 6 F 2 S 0 8 7 7 Appendix C Signal List ...
Page 103: ... 102 6 F 2 S 0 8 7 7 ...
Page 104: ... 103 6 F 2 S 0 8 7 7 Appendix D Setting Sheet 1 Relay Unit Identification 2 Default setting ...
Page 118: ... 117 6 F 2 S 0 8 7 7 Appendix E Return Repair Form ...
Page 121: ... 120 6 F 2 S 0 8 7 7 ...
Page 122: ... 121 6 F 2 S 0 8 7 7 Appendix F Technical Data ...
Page 125: ... 124 6 F 2 S 0 8 7 7 ...
Page 126: ... 125 6 F 2 S 0 8 7 7 Appendix G Ordering ...
Page 129: ......