21
6 F 2 S 0 8 7 7
4.2.3.5 IEC60870-5-103 and IEC61850 setting
The following items related IEC60870-5-103 are set:
IEC60870-5-103 retry: set the retry times within the range of 0 to 5.
IEC60870-5-103 polling: set the polling time within the range of 0 to 200ms.
IEC60870-5-103 loop: set the loop delay time within the range of 0 to 200ms.
IEC60870-5-103 timeout: set the receive timeout time within the range of 50 to 30000ms.
IEC60870-5-103 sigrst: set the reset time for only On signal within the range of 0.1 to 10.0s.
IEC61850 block: select “Blocked” to block the monitor direction.
IEC61850 auth: select “On” to use the authentication function.
IEC61850 deadtm: set the dead time within the range of 10 to 120min.
IEC61850 deadband: set the measurement dead band within the range of 0.1 to 10.0%.
GOODE interval: set the max. GOOSE sending period within the range of 1 to 10s.
Ping check: select “On” to execute Ping response check.
GOOSE check: select “On” to execute GOOSE receive check.
SC check: select “On” to execute Server connect check.
TSCCOMF: set the Server connect checkout time within the range of 0 to 60s.
Summary of Contents for G1IF4
Page 29: ... 28 6 F 2 S 0 8 7 7 4 2 9 Active group Active group Group 1 fixed ...
Page 34: ... 33 6 F 2 S 0 8 7 7 IFU side setting ...
Page 35: ... 34 6 F 2 S 0 8 7 7 And then check the connecting status by RSM100 ...
Page 48: ... 47 6 F 2 S 0 8 7 7 Appendix A External Connections ...
Page 50: ... 49 6 F 2 S 0 8 7 7 Appendix B Outline Diagram ...
Page 52: ... 51 6 F 2 S 0 8 7 7 Appendix C Signal List ...
Page 103: ... 102 6 F 2 S 0 8 7 7 ...
Page 104: ... 103 6 F 2 S 0 8 7 7 Appendix D Setting Sheet 1 Relay Unit Identification 2 Default setting ...
Page 118: ... 117 6 F 2 S 0 8 7 7 Appendix E Return Repair Form ...
Page 121: ... 120 6 F 2 S 0 8 7 7 ...
Page 122: ... 121 6 F 2 S 0 8 7 7 Appendix F Technical Data ...
Page 125: ... 124 6 F 2 S 0 8 7 7 ...
Page 126: ... 125 6 F 2 S 0 8 7 7 Appendix G Ordering ...
Page 129: ......