Toshiba G1IF4 Instruction Manual Download Page 40

 

 

39

 

 

 

6  F  2  S  0  8  7  7 

Customize 

Add IEC-103 signal: 

Start the IEC103 configurator tool and edit the defined file. Then, write the edited result into the 
relay. Next, update the IEC-103 file by the IFU engineering tool. 

 

 

Summary of Contents for G1IF4

Page 1: ...6 F 2 S 0 8 7 7 INSTRUCTION MANUAL INTERFACE UNIT G1IF4 Toshiba Energy Systems Solutions Corporation 2017 All Rights Reserved Ver 2 1 ...

Page 2: ...be followed by important safety information that must be carefully reviewed Indicates an imminently hazardous situation which will result in death or serious injury if you do not follow the instructions Indicates a potentially hazardous situation which could result in death or serious injury if you do not follow the instructions CAUTION Indicates a potentially hazardous situation which if not avoi...

Page 3: ...ting environment The equipment must only used within the range of ambient temperature humidity and dust detailed in the specification and in an environment free of abnormal vibration Ratings Before applying AC or DC voltage to the equipment check that they conform to the equipment ratings Connection cable Carefully handle the connection cable without applying excessive force Unit Do not disassembl...

Page 4: ...ary Output Module 12 3 2 Binary Input and Output Signals 13 3 2 1 Binary input signals 13 3 2 2 Binary output signals 13 3 3 PLC Programmable Logic Controller Function 14 3 4 IEC61850 Function 14 4 Operation 15 4 1 Preparation 15 4 2 Setting 16 4 2 1 Version 16 4 2 2 Description 17 4 2 3 Communication 18 4 2 4 Event record 22 4 2 5 Status 23 4 2 6 Binary input 26 4 2 7 Binary output 26 4 2 8 Confi...

Page 5: ...Connections 43 6 Commissioning and Maintenance 44 6 1 General 44 6 2 Precautions 44 6 3 Preparation 44 6 4 Commissioning Procedure 44 6 5 Maintenance 45 6 6 Storage 45 7 Putting Unit into Service 46 Appendix A 47 External Connections 47 Appendix B 49 Outline Diagram 49 Appendix C 51 Signal List 51 Appendix D 103 Setting Sheet 103 Appendix E 117 Return Repair Form 117 Appendix F 121 Technical Data ...

Page 6: ... Model Type 1A TESTING ALARM IN SERVICE TRIP Metering 1 Ia 1 Ib 1 Ic 1 0 50 A 0 50 A 0 50 A Ia 2 Ib 2 Ic 2 0 50 A 0 50 A 0 50 A 7 8 9 4 5 6 1 2 3 0 END CAN CEL ENTER TRANSFORMER PR OTEC TION In 1 In 2 0 01 A 0 01 A TOSHIBA B A 0V VIEW RESET Vn 100 110 115 120 V MADE IN JAPAN 110 125 V DC Vdc fn 50 Hz GRT100 201 B 10 10 In Model Type 1A TESTING ALARM IN SERVICE TRIP Metering 1 Ia 1 Ib 1 Ic 1 0 50 A...

Page 7: ...o Master function of IEC60870 5 103 provided with G1IF4 If a protection relay without IEC61850 but with Slave function of IEC60870 5 103 is connected to G1IF4 the G1IF4 can convert data between IEC60870 5 103 and IEC61850 Vn Made i n Japan 110 125DC Vdc fn G1IF 4 101 A 10 L0 In Model Type TEST IN SERVICE ALARM INTER FACE UNIT TOSHIBA LAN CONN FAIL TIME SYNC LOSS RS 485 1 FAIL DB WRITING FAIL B A 0...

Page 8: ...port Vn Made i n Japan 110 125DC Vdc fn G1IF 4 101 A 10 L0 In Model Type TEST IN SERVICE ALARM INTER FACE UNIT TOSHIBA LAN CONN FAIL TIME SYNC LOSS RS 485 1 FAIL DB WRITING FAIL B A 0V VIEW RESET Vn 100 110 115 120 V MADE IN JAPAN 110 125 V DC Vdc fn 50 Hz GRT100 201 B 10 10 In Model Type 1A TESTING ALARM IN SERVICE TRIP Metering 1 Ia 1 Ib 1 Ic 1 0 50 A 0 50 A 0 50 A Ia 2 Ib 2 Ic 2 0 50 A 0 50 A 0...

Page 9: ... synchronisation network is interrupted the internal clock runs locally 2 3 2 Human Interface The front panel of the G1IF4 incorporates the following human interfaces Two fixed logic Light Emitting Diodes LEDs and twelve configurable logic LEDs The two fix logic LEDs are used to display the following signals IN SERVICE Green ALARM Red The colour of the twelve configurable logic LEDs can be selecte...

Page 10: ...detects failures that might occur within G1IF4 The following items are monitored by the automatic supervision function Binary input and output circuits Communication circuits for the station LAN IEC60870 5 103 transmission network Processor Watch Dog timer Memory DC power supply circuit When failures are detected by automatic monitoring the ALARM LED on the front panel is turned on and also detail...

Page 11: ...ion Items and Alarms Supervision Item LED IN SERVICE LED ALARM Ext alarm Event record Message CPU Memory monitoring Off On 1 Relay fail Watchdog Timer Off On 1 Relay fail DC supply monitoring 2 On Relay fail A PLC data or IEC61850 mapping data monitoring On On Relay fail A GOOSE message check On On Relay fail A Ping response check On On Relay fail A 1 The binary output relay FAIL operates 2 It dep...

Page 12: ... 128 1 100 Number of bi trigger on off events EV1 EV128 0 3071 Assign the signal number Up to 1024 records can be stored If an additional event occurs when 1024 records have been stored the oldest event record is deleted and the latest event record is then stored ...

Page 13: ... Comm port Ethernet Figure 3 1 Hardware block diagram 3 1 1 Signal Processing Module Microprocessors and communication control circuits for the station LAN are integrated into one module as a signal processing module 100Base TX and 100Base FX for LAN I F are provided Either of them can be activated by setting A 64 bit RISC processor is used to perform dedicated functions in the G1IF4 3 1 2 Binary ...

Page 14: ...c PLC BI1 command Sign BISW1 1 Inv Norm 1 Inv Norm BISW2 1 Inv Norm BISWn BI2 command BI39 command PLC input PLC output Figure 3 2 1 Binary Input Circuit 3 2 2 Binary output signals The signals shown in the signal list in Appendix C can be assigned to the output relay individually or in arbitrary combinations Signals can be combined using either an AND circuit or OR circuit with 6 gates each as sh...

Page 15: ...gurable binary inputs binary outputs and LEDs are programmed by the PLC function Temporary signals are provided for complicated logics or for using a user configured signal in many logic sequences For PLC tool refer to PLC tool instruction manual Figure 3 4 1 Sample Screen of PLC Tool 3 4 IEC61850 Function G1IF4 supports the following IEC61850 functions Display status value Report function GOOSE f...

Page 16: ... instruction manual No 6F2S0715 4 1 Preparation Connect the G1IF4 and a PC by the RS232C cable or Ethernet Supply DC power to the G1IF4 Start the RSM100 software on the PC and open the Startup Top menu screen And then select the G1IF4 INTERFACE UNIT IN SERVICE ALARM TEST LAN CONN FAIL TIME SYNC LOSS RS485 1 FAIL RS485 2 FAIL DB WRITING FAIL Figure 4 1 Connecting between G1IF4 and PC ...

Page 17: ...unication port baud rate Logical device address Test mode etc Record Status Binary input Binary output Configurable LED Active group The settings of the interface unit G1IF4 is performed as follows Figure 4 2 Top menu Screen 4 2 1 Version Click the Setting button on the Top menu Screen and click the Version on the Setting menu Screen ...

Page 18: ...ly screen appears This screen displays Relay type Serial No and Version of installed software 4 2 2 Description Plant name Description and Event name can be set Click the Description on the Setting menu Screen Then the Description screen appears ...

Page 19: ...andum and Event name 4 2 3 Communication Communication port baud rate Logical device address and Test mode etc can be set Click the Communication on the Setting menu Screen Then the Communication screen appears 4 2 3 1 Communication port baud rate Select the baud rate and Ethernet device in the New column ...

Page 20: ...to this IFU in the network configured by IEC60870 5 103 communication 4 2 3 3 IP address Subnet mask Default gateway SNTP server address Enter IP address for IP1 1 to IP2 4 Subnet mask for SM1 1 to SM2 4 Default gateway for GW1 1 to GW2 4 and SNTP server address for SI1 1 to SI4 4 IP SM and GW are available for two ports depending on the model Four SNTP servers are available Example IP address IP1...

Page 21: ... 20 6 F 2 S 0 8 7 7 4 2 3 4 Test mode of logical device If testing a Logical device set Test mode item and the tested logical device to On In normal condition set them to Off ...

Page 22: ...et the reset time for only On signal within the range of 0 1 to 10 0s IEC61850 block select Blocked to block the monitor direction IEC61850 auth select On to use the authentication function IEC61850 deadtm set the dead time within the range of 10 to 120min IEC61850 deadband set the measurement dead band within the range of 0 1 to 10 0 GOODE interval set the max GOOSE sending period within the rang...

Page 23: ...s The following items are set BITRN Enter the number of events for which both status changes On and Off are recorded If 20 is set both status changes are recorded for EV1 to EV20 events and only the status change to On is recorded for EV21 to EV128 events EV Enter the signal number to record as the event in Appendix C ...

Page 24: ...e Time zone Line parameter for Fault location Auroreclose success information Autoreclose in progress information Autoreclose ready information 4 2 5 1 Time synchronisation source Time sync Select SNTP to be synchronised by a SNTP server 4 2 5 2 Time zone GMT and GMTm Enter the difference between GMT and local time Enter a numerical value to GMT hrs and GMTm min ...

Page 25: ...D FLrate Set the LD FLrate 1 000 Note Default setting value is 1 000 If the fault location result is reported as an impedance from IEC60870 5 103 Fault location value FltDiskm mag f Measurement value in IEC103 LD FLrate Set the LD FLrate 1 Line impedance per km 2 In case of the fault impedance FltZ If the fault location result is reported as a distance km from IEC60870 5 103 Fault location value F...

Page 26: ... 256 LD ARC1 for CB1 LD ARC2 for CB2 4 2 5 5 Auroreclose in progress information LD ARC1 I INF LD ARC2 I INF Enter the autoreclose in progress information number of the selected Logical device within the range of 0 to 256 4 2 5 6 Auroreclose ready information LD ARC1 R INF LD ARC2 R INF Enter the autoreclose ready information number of the selected Logical device within the range of 0 to 256 ...

Page 27: ...ORing signals to one output relay Available signals are listed in Appendix C It is also possible to attach a delayed drop off delay time of 0 2 seconds to these signals The delay drop off time is disabled by the scheme switch BOTD Click the Binary output on the Setting menu Screen Then the IO 2 Binary output screen appears The following items are set OP Logic select OR or AND to use an OR gate or ...

Page 28: ... gate or AND gate operation of LED G and LED R If OR gate selected and both LED G and LED R driven its LED colour is yellow Further each LED has a programmable reset characteristic settable for instantaneous drop off or for latching operation The signals listed in Appendix C can be assigned to each LED The following items are set LED _ Logic select OR or AND to use an OR gate or AND gate LED _ Res...

Page 29: ... 28 6 F 2 S 0 8 7 7 4 2 9 Active group Active group Group 1 fixed ...

Page 30: ...ord data are extracted from the G1IF4 and the following event record screen appears The event records are displayed in order of new to old The event records saved in the G1IF4 can be cleared from the PC in the on line operation as follows Click the Clear record tab on the record screen and then click the Clear button ...

Page 31: ...data are extracted from the G1IF4 and the following status screen appears Then click the tab to display In the LED Comm tab the status of LED is displayed by G R or Y Green Red or Yellow The reversed display shows the lighting status If clicking the Latch Reset button the latched LEDs are reset The lamp test of LEDs is performed by clicking the Lamp Test button The status of communication is displ...

Page 32: ... test It is possible to forcibly operate all binary output relays for checking connections with the external devices Forced operation can be performed on one or more binary outputs at a time for each module Click the Binary output tab to open the screen If forcibly operating binary output set the New column to Enable on the line of a binary output module and output number And click the Test on but...

Page 33: ...ay by using RS485 port 4 6 2 Address setting Set the same address on the G1IF4 as that of IEC60870 5 103 on the relay side If RSM100 is also connected then set the address of HDLC to the same Set the same communication speed baud rate of the G1IF4 as that of the relay In case of the G1IF4 with one RS485 port set the protocol to IEC Because the RSM100 cannot be connected disturbance records cannot ...

Page 34: ... 33 6 F 2 S 0 8 7 7 IFU side setting ...

Page 35: ... 34 6 F 2 S 0 8 7 7 And then check the connecting status by RSM100 ...

Page 36: ...engineering tool For details of IFU engineering tool see the instruction manual of IFU engineering tool Start the IFU engineering tool Startup screen Reading initial data Click Open Read the IFU default data without IEC60870 5 103 connection After reading the following screen appears ...

Page 37: ...ct Add IEC103 Input the device name to add Any name is OK because the data is overwritten when importing After input the Logical device LLN0 and LPHD1 is automatically created as follows Importing default data Select the device to import right click and select the Import Logical Device ...

Page 38: ... 37 6 F 2 S 0 8 7 7 Select the default setting data Select the logical device information written from the default setting data After reading the following screen appears ...

Page 39: ...ata Click the Send button to write the setting data into the IFU If the Logical node data SCL is changed restart the IFU and read the setting data again When some devices are defined the definition order of the device and the definition order of the IEC 103 address must be the same This shows the definition for the IED1 ...

Page 40: ...6 F 2 S 0 8 7 7 Customize Add IEC 103 signal Start the IEC103 configurator tool and edit the defined file Then write the edited result into the relay Next update the IEC 103 file by the IFU engineering tool ...

Page 41: ...e signals cannot be output in some relay types In this case only the signal Autoreclose Success is available Condition ARC S INF INF number specified ARC I INF and ARC R INF INF number not specified If above condition is satisfied it functions as follows Autoreclose success on Autoreclose status value 3 Autoreclose success off Autoreclose status value 1 4 7 2 Fault location value km Z Z km convers...

Page 42: ...rement value In accordance with IEC103 measurands are transmitted every second while in IEC61850 only changes in value are reported In order to avoid repeated transmissions due to insignificant changes in value a DEADBAND setting is provided Data on the IEC61850 side is updated only when the measurement value reported by IEC103 has changed by more than DEADBAND setting IEC 103 Measurement value 40...

Page 43: ...us damage which often may not be immediately apparent but the reliability of the circuit will have been reduced The electronic circuits are completely safe from electrostatic discharge when housed in the case Do not expose them to risk of damage by removing the PCB unnecessarily The unit incorporates the highest practicable protection for its semiconductor devices However if it becomes necessary t...

Page 44: ...inal block TB4 The power supply and safety earth connections should be made with P N and E terminal Releasing Socket Connector of Terminal Block The socket connector cable side of the terminal block is releasable for maintenance etc When releasing it or inserting it proceed as follows When releasing it Never pull the connected wire s Release the socket connector using the top and bottom release le...

Page 45: ...above may cause damage or malfunction of the unit Refer to section 5 4 for information on handling precautions 6 3 Preparation Test equipment The following test equipment is required for the commissioning tests DC or AC power supply Calibrated voltmeter PC Visual inspection After unpacking the product check for any damage to the case If there is any damage the internal module might also have been ...

Page 46: ... maintenance is not necessary 6 6 Storage The spare unit should be stored in a dry and clean room Based on IEC Standard 60255 0 the storage temperature should be 25 C to 70 C but the temperature of 0 C to 40 C is recommended for long term storage ...

Page 47: ... tests Check that all external connections are correct Check the setting of all elements recordings and clock are correct In particular when settings are changed temporarily for testing be sure to restore them Clear any unnecessary records on events which are recorded during the tests Check that the green IN SERVICE LED is lit and no other LEDs are lit on the front panel ...

Page 48: ... 47 6 F 2 S 0 8 7 7 Appendix A External Connections ...

Page 49: ...34 TB2 14 BI35 TB2 15 BI36 BI37 TB2 17 BI38 TB2 18 BI39 TB2 19 TB2 16 TB3 9 TB3 10 BO2 TB3 7 TB3 8 BO1 Binary Output TB3 13 TB3 14 BO4 TB3 11 TB3 12 BO3 TB3 17 TB3 18 BO6 TB3 15 TB3 16 BO5 TB4 1 TB4 2 BO8 TB3 19 TB3 20 BO7 TB4 5 TB4 6 BO10 TB4 3 TB4 4 BO9 TB4 9 TB4 10 BO12 TB4 7 TB4 8 BO11 TB4 12 TB4 13 BO13 TB4 11 TB4 18 TB4 19 TB4 20 RS485 2 for IEC60870 5 103 TB4 15 TB4 16 TB4 17 RS485 1 for RS...

Page 50: ... 49 6 F 2 S 0 8 7 7 Appendix B Outline Diagram ...

Page 51: ...70 112 Panel cutout INTERFACE UNIT IN SERVICE ALARM TEST LAN CONN FAIL TIME SYNC LOSS RS485 1 FAIL RS485 2 FAIL DB WRITING FAIL RS 232C 286 110 Front view Rating label Rear view LAN port RJ45 100BASE TX Terminal block TB1 TB2 TB3 TB4 13 4 15 LAN port SC 100BASE FX Option Option T1 T2 F1 F2 E ...

Page 52: ... 51 6 F 2 S 0 8 7 7 Appendix C Signal List ...

Page 53: ...N_CONN_FAIL LAN_CONN_FAIL 6 7 TIME_SYNC_LOSS TIME_SYNC_LOSS 8 HDLC_FAILED HDLC_FAILED 9 IEC103_FAILED IEC103_FAILED 10 DB_WRITING_FAIL DB_WRITING_FAIL 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 240 ...

Page 54: ... RLYFAIL RELAY FAILURE 255 RLY_O P_BLK RELAY OUTPUT BLOCK 256 SV LOCK SV BLOCK 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 400 ...

Page 55: ...ROG01_10 412 MPROG01_11 413 MDOW100_00 414 MDOW100_01 415 MDOW100_02 416 MDOW100_03 417 MDOW100_04 418 MDOW100_05 419 MDOW100_06 420 MDOW100_07 421 MDOW100_08 422 MDOW100_09 423 MDOW100_10 424 MDOW100_11 425 426 427 428 429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 451 452 453 454 455 456 457 458 459 460 461 462 463 464 465 466 467 468 469 470 471 472 473 ...

Page 56: ...MAND Binary input signal BI16 529 BI17_COMMAND Binary input signal BI17 530 BI18_COMMAND Binary input signal BI18 531 BI19_COMMAND Binary input signal BI19 532 BI20_COMMAND Binary input signal BI20 533 BI21_COMMAND Binary input signal BI21 534 BI22_COMMAND Binary input signal BI22 535 BI23_COMMAND Binary input signal BI23 536 BI24_COMMAND Binary input signal BI24 537 BI25_COMMAND Binary input sign...

Page 57: ... BO3 select 2 777 BO4_SELV_0 BO4 select 0 778 BO4_SELV_1 BO4 select 1 779 BO4_SELV_2 BO4 select 2 780 BO5_SELV_0 BO5 select 0 781 BO5_SELV_1 BO5 select 1 782 BO5_SELV_2 BO5 select 2 783 BO6_SELV_0 BO6 select 0 784 BO6_SELV_1 BO6 select 1 785 BO6_SELV_2 BO6 select 2 786 BO7_SELV_0 BO7 select 0 787 BO7_SELV_1 BO7 select 1 788 BO7_SELV_2 BO7 select 2 789 BO8_SELV_0 BO8 select 0 790 BO8_SELV_1 BO8 sel...

Page 58: ...O6 control 2 834 BO7_OPEV_0 BO7 control 0 835 BO7_OPEV_1 BO7 control 1 836 BO7_OPEV_2 BO7 control 2 837 BO8_OPEV_0 BO8 control 0 838 BO8_OPEV_1 BO8 control 1 839 BO8_OPEV_2 BO8 control 2 840 BO9_OPEV_0 BO9 control 0 841 BO9_OPEV_1 BO9 control 1 842 BO9_OPEV_2 BO9 control 2 843 BO10_OPEV_0 BO10 control 0 844 BO10_OPEV_1 BO10 control 1 845 BO10_OPEV_2 BO10 control 2 846 BO11_OPEV_0 BO11 control 0 84...

Page 59: ...select issue 892 BO10_SIGOPR BO10 operate issue 893 BO10_SIGCAN BO10 cancel issue 894 BO11_SIGSEL BO11 select issue 895 BO11_SIGOPR BO11 operate issue 896 BO11_SIGCAN BO11 cancel issue 897 BO12_SIGSEL BO12 select issue 898 BO12_SIGOPR BO12 operate issue 899 BO12_SIGCAN BO12 cancel issue 900 BO13_SIGSEL BO13 select issue 901 BO13_SIGOPR BO13 operate issue 902 BO13_SIGCAN BO13 cancel issue 903 904 9...

Page 60: ...7 1248 1249 1250 1251 RLY_FAIL RELAY FAILURE 1252 RLY_OP_BLK RELAY OUTPUT BLOCK 1253 AMF_OFF SV BLOCK 1254 1255 1256 1257 1258 RELAY_FAIL A RELAY_FAIL A 1259 1260 1261 LD1_Offline LD1_Offline 1262 LD2_Offline LD2_Offline 1263 LD3_Offline LD3_Offline 1264 LD4_Offline LD4_Offline 1265 LD5_Offline LD5_Offline 1266 LD6_Offline LD6_Offline 1267 LD7_Offline LD7_Offline 1268 LD8_Offline LD8_Offline 1269 ...

Page 61: ... BI30 unfiltered 1314 BI31_COM_UF Binary input signal BI31 unfiltered 1315 BI32_COM_UF Binary input signal BI32 unfiltered 1316 BI33_COM_UF Binary input signal BI33 unfiltered 1317 BI34_COM_UF Binary input signal BI34 unfiltered 1318 BI36_COM_UF Binary input signal BI35 unfiltered 1319 BI36_COM_UF Binary input signal BI36 unfiltered 1320 BI37_COM_UF Binary input signal BI37 unfiltered 1321 BI38_CO...

Page 62: ...ut 34 1384 GOOSE_IN_25 Goose Input 25 1385 GOOSE_IN_26 Goose Input 26 1386 GOOSE_IN_27 Goose Input 27 1387 GOOSE_IN_28 Goose Input 28 1388 GOOSE_IN_29 Goose Input 29 1389 GOOSE_IN_30 Goose Input 30 1390 GOOSE_IN_31 Goose Input 31 1391 GOOSE_IN_32 Goose Input 32 1392 1393 1394 1395 1396 1397 1398 1399 1400 1401 1402 1403 NORM_LED_ON IN SERVICE LED ON 1404 ALM_LED_ON ALARM LED ON 1405 1406 1407 1408...

Page 63: ... error 1475 BU_RAM_err BU RAM memory monitoring error 1476 1477 EEPROM_err EEPROM memory monitoring error 1478 1479 1480 CPU_err Program error 1481 Invalid Invalid error 1482 NMI NMI 1483 Sampling_err Sampling error 1484 DIO_err DIO card connection error 1485 LAN_err LAN error 1486 1487 ROM_data_err 8M Romdata error 1488 1489 1490 1491 1492 1493 1494 1495 1496 1497 1498 1499 1500 1501 1502 1503 15...

Page 64: ... PRG_LED8_G_ON PROGRAMMABLELED8 ON Green 1526 PRG_LED8_R_ON PROGRAMMABLELED8 ON Red 1527 PRG_LED9_G_ON PROGRAMMABLELED9 ON Green 1528 PRG_LED9_R_ON PROGRAMMABLELED9 ON Red 1529 PRG_LED10_G_ON PROGRAMMABLELED10 ON Green 1530 PRG_LED10_R_ON PROGRAMMABLELED10 ON Red 1531 PRG_LED11_G_ON PROGRAMMABLELED11 ON Green 1532 PRG_LED11_R_ON PROGRAMMABLELED11 ON Red 1533 PRG_LED12_G_ON PROGRAMMABLELED12 ON Gre...

Page 65: ...545 1546 1547 1548 1549 1550 1551 1552 1553 1554 1555 1556 1557 1558 1559 1560 1561 1562 1563 1564 1565 1566 1567 1568 1569 1570 1571 1572 1573 1574 1575 1576 1577 1578 1579 1580 1581 1582 1583 1584 1585 1586 1587 1588 1589 1590 1591 1592 1593 1594 1595 1596 1597 1598 1599 1600 1601 1602 1603 1604 1605 1606 1607 1790 ...

Page 66: ...al 7 1799 BO8_OUT Binary output signal 8 1800 BO9_OUT Binary output signal 9 1801 BO10_OUT Binary output signal 10 1802 BO11_OUT Binary output signal 11 1803 BO12_OUT Binary output signal 12 1804 1805 1806 1807 1808 1809 1810 1811 1812 1813 1814 1815 1816 1817 1818 1819 1820 1821 1822 1823 1824 1825 1826 1827 1828 1829 1830 1831 1832 1833 1834 1835 1836 1837 1838 1839 1840 1841 1842 1843 1844 1845...

Page 67: ..._UP_SIG CNT8_UP_SIG 1928 CNT9_UP_SIG CNT9_UP_SIG 1929 CNT10_UP_SIG CNT10_UP_SIG 1930 CNT11_UP_SIG CNT11_UP_SIG 1931 CNT12_UP_SIG CNT12_UP_SIG 1932 CNT13_UP_SIG CNT13_UP_SIG 1933 CNT14_UP_SIG CNT14_UP_SIG 1934 CNT15_UP_SIG CNT15_UP_SIG 1935 CNT16_UP_SIG CNT16_UP_SIG 1936 CNT17_UP_SIG CNT17_UP_SIG 1937 CNT18_UP_SIG CNT18_UP_SIG 1938 CNT19_UP_SIG CNT19_UP_SIG 1939 CNT20_UP_SIG CNT20_UP_SIG 1940 CNT21...

Page 68: ...CNT8_RST_SIG CNT8_RST_SIG 1992 CNT9_RST_SIG CNT9_RST_SIG 1993 CNT10_RST_SIG CNT10_RST_SIG 1994 CNT11_RST_SIG CNT11_RST_SIG 1995 CNT12_RST_SIG CNT12_RST_SIG 1996 CNT13_RST_SIG CNT13_RST_SIG 1997 CNT14_RST_SIG CNT14_RST_SIG 1998 CNT15_RST_SIG CNT15_RST_SIG 1999 CNT16_RST_SIG CNT16_RST_SIG 2000 CNT17_RST_SIG CNT17_RST_SIG 2001 CNT18_RST_SIG CNT18_RST_SIG 2002 CNT19_RST_SIG CNT19_RST_SIG 2003 CNT20_RS...

Page 69: ...2_EXE_WAIT BO2 operate condition wait 2071 2072 BO2_RES_OK BO2 operate success 2073 BO2_RES_NG BO2 operate error 2074 BO2_RES_WAIT BO2 operate wait 2075 BO2_CAUSE_0 BO2 addcouse bit0 2076 BO2_CAUSE_1 BO2 addcouse bit1 2077 BO2_CAUSE_2 BO2 addcouse bit2 2078 BO2_CAUSE_3 BO2 addcouse bit3 2079 BO2_CAUSE_4 BO2 addcouse bit4 2080 BO3_SEL_OK BO3 select success 2081 BO3_SEL_NG BO3 select error 2082 BO3_...

Page 70: ...lect wait 2147 2148 BO7_EXE_OK BO7 operare condition success 2149 BO7_EXE_NG BO7 operate condition error 2150 BO7_EXE_WAIT BO7 operate condition wait 2151 2152 BO7_RES_OK BO7 operate success 2153 BO7_RES_NG BO7 operate error 2154 BO7_RES_WAIT BO7 operate wait 2155 BO7_CAUSE_0 BO7 addcouse bit0 2156 BO7_CAUSE_1 BO7 addcouse bit1 2157 BO7_CAUSE_2 BO7 addcouse bit2 2158 BO7_CAUSE_3 BO7 addcouse bit3 ...

Page 71: ... bit1 2221 BO11_CAUSE_2 BO11 addcouse bit2 2222 BO11_CAUSE_3 BO11 addcouse bit3 2223 BO11_CAUSE_4 BO11 addcouse bit4 2224 BO12_SEL_OK BO12 select success 2225 BO12_SEL_NG BO12 select error 2226 BO12_SEL_WAIT BO12 select w ait 2227 2228 BO12_EXE_OK BO12 operare condition success 2229 BO12_EXE_NG BO12 operate condition error 2230 BO12_EXE_WAIT BO12 operate condition w ait 2231 2232 BO12_RES_OK BO12 ...

Page 72: ...w er value bit0 2320 BO6_ANS_SELV2 BO6 select answ er value bit1 2321 BO6_ANS_SELV0 BO6 select answ er value bit2 2322 BO7_ANS_SELV1 BO7 select answ er value bit0 2323 BO7_ANS_SELV2 BO7 select answ er value bit1 2324 BO7_ANS_SELV0 BO7 select answ er value bit2 2325 BO8_ANS_SELV1 BO8 select answ er value bit0 2326 BO8_ANS_SELV2 BO8 select answ er value bit1 2327 BO8_ANS_SELV0 BO8 select answ er val...

Page 73: ...OS2_B DPOS2_B Off 2404 DPOS3_A DPOS3_A On 2405 DPOS3_B DPOS3_B Off 2406 DPOS4_A DPOS4_A On 2407 DPOS4_B DPOS4_B Off 2408 DPOS5_A DPOS5_A On 2409 DPOS5_B DPOS5_B Off 2410 DPOS6_A DPOS6_A On 2411 DPOS6_B DPOS6_B Off 2412 DPOS7_A DPOS7_A On 2413 DPOS7_B DPOS7_B Off 2414 DPOS8_A DPOS8_A On 2415 DPOS8_B DPOS8_B Off 2416 DPOS9_A DPOS9_A On 2417 DPOS9_B DPOS9_B Off 2418 DPOS10_A DPOS10_A On 2419 DPOS10_B...

Page 74: ...41 2442 2443 2444 2445 2446 2447 2448 2449 2450 2451 2452 2453 2454 2455 2456 2457 2458 2459 2460 2461 2462 2463 2464 2465 2466 2467 2468 2469 2470 2471 2472 2473 2474 2475 2476 2477 2478 2479 2480 2481 2482 2483 2484 2485 2486 2487 2488 2489 2490 2491 2492 2493 2494 2495 2496 2497 2498 2499 2500 2501 2502 2503 2504 2505 2506 2507 2508 2509 2510 ...

Page 75: ...TSTMOD_2 2563 SIG_TSTMOD_3 2564 SIG_TSTMOD_4 2565 SIG_TSTMOD_5 2566 SIG_TSTMOD_6 2567 SIG_TSTMOD_7 2568 SIG_TSTMOD_8 2569 SIG_TSTMOD_9 2570 SIG_TSTMOD_10 2571 RESET_LED 2572 LAMPTEST 2573 2574 2575 2576 SIG_BO_1 BO 1 control out 2577 SIG_BO_2 BO 2 control out 2578 SIG_BO_3 BO 3 control out 2579 SIG_BO_4 BO 4 control out 2580 SIG_BO_5 BO 5 control out 2581 SIG_BO_6 BO 6 control out 2582 SIG_BO_7 BO...

Page 76: ...06 2607 2608 2609 2610 ALARM_LED_SET Alarm LED set 2611 2612 2613 2614 2615 2616 2617 2618 2619 2620 2621 2622 2623 2624 2625 2626 2627 2628 2629 2630 2631 2632 2633 2634 2635 2636 2637 2638 2639 2640 2641 2642 2643 2644 2645 2646 2647 2648 2649 2650 2651 2652 2653 2654 2655 2656 2657 2658 2659 2660 2661 2662 2663 2664 2665 2666 2667 2668 2669 2670 ...

Page 77: ...3 2684 2685 2686 2687 2688 2689 2690 2691 2692 2693 2694 2695 2696 2697 2698 2699 2700 2701 2702 2703 2704 2705 2706 2707 2708 2709 2710 2711 2712 2713 2714 2715 2716 2717 2718 2719 2720 2721 2722 2723 2724 2725 2726 2727 2728 2729 2730 2731 2732 2733 2734 2735 2736 2737 2738 2739 2740 2741 2742 2743 2744 2745 2746 2747 2748 2749 2750 ...

Page 78: ...5 2776 2777 2778 2779 2780 2781 2782 2783 2784 2785 2786 2787 2788 2789 2790 2791 2792 2793 2794 2795 2796 2797 2798 2799 2800 2801 2802 2803 2804 2805 2806 2807 2808 2809 2810 2811 2812 2813 2814 2815 2816 TEMP001 2817 TEMP002 2818 TEMP003 2819 TEMP004 2820 TEMP005 2821 TEMP006 2822 TEMP007 2823 TEMP008 2824 TEMP009 2825 TEMP010 2826 TEMP011 2827 TEMP012 2828 TEMP013 2829 TEMP014 2830 TEMP015 ...

Page 79: ...EMP045 2861 TEMP046 2862 TEMP047 2863 TEMP048 2864 TEMP049 2865 TEMP050 2866 TEMP051 2867 TEMP052 2868 TEMP053 2869 TEMP054 2870 TEMP055 2871 TEMP056 2872 TEMP057 2873 TEMP058 2874 TEMP059 2875 TEMP060 2876 TEMP061 2877 TEMP062 2878 TEMP063 2879 TEMP064 2880 TEMP065 2881 TEMP066 2882 TEMP067 2883 TEMP068 2884 TEMP069 2885 TEMP070 2886 TEMP071 2887 TEMP072 2888 TEMP073 2889 TEMP074 2890 TEMP075 289...

Page 80: ...EMP125 2941 TEMP126 2942 TEMP127 2943 TEMP128 2944 TEMP129 2945 TEMP130 2946 TEMP131 2947 TEMP132 2948 TEMP133 2949 TEMP134 2950 TEMP135 2951 TEMP136 2952 TEMP137 2953 TEMP138 2954 TEMP139 2955 TEMP140 2956 TEMP141 2957 TEMP142 2958 TEMP143 2959 TEMP144 2960 TEMP145 2961 TEMP146 2962 TEMP147 2963 TEMP148 2964 TEMP149 2965 TEMP150 2966 TEMP151 2967 TEMP152 2968 TEMP153 2969 TEMP154 2970 TEMP155 297...

Page 81: ...3021 TEMP206 3022 TEMP207 3023 TEMP208 3024 TEMP209 3025 TEMP210 3026 TEMP211 3027 TEMP212 3028 TEMP213 3029 TEMP214 3030 TEMP215 3031 TEMP216 3032 TEMP217 3033 TEMP218 3034 TEMP219 3035 TEMP220 3036 TEMP221 3037 TEMP222 3038 TEMP223 3039 TEMP224 3040 TEMP225 3041 TEMP226 3042 TEMP227 3043 TEMP228 3044 TEMP229 3045 TEMP230 3046 TEMP231 3047 TEMP232 3048 TEMP233 3049 TEMP234 3050 TEMP235 3051 TEMP2...

Page 82: ...km LD6_FltDiskm 27 LD7_FltDiskm LD7_FltDiskm 28 LD8_FltDiskm LD8_FltDiskm 29 LD9_FltDiskm LD9_FltDiskm 30 LD10_FltDiskm LD10_FltDiskm 31 MEASURE_032 MEASURE_032 32 MEASURE_033 MEASURE_033 33 MEASURE_034 MEASURE_034 34 MEASURE_035 MEASURE_035 35 MEASURE_036 MEASURE_036 36 MEASURE_037 MEASURE_037 37 MEASURE_038 MEASURE_038 38 MEASURE_039 MEASURE_039 39 MEASURE_040 MEASURE_040 40 MEASURE_041 MEASURE_...

Page 83: ...FREV IFU_CONFREV 41 IED1_CONFREV IED1_CONFREV 42 IED2_CONFREV IED2_CONFREV 43 IED3_CONFREV IED3_CONFREV 44 IED4_CONFREV IED4_CONFREV 45 IED5_CONFREV IED5_CONFREV 46 IED6_CONFREV IED6_CONFREV 47 IED7_CONFREV IED7_CONFREV 48 IED8_CONFREV IED8_CONFREV 49 IED9_CONFREV IED9_CONFREV 50 IED10_CONFREV IED10_CONFREV 51 52 53 54 55 56 57 58 59 60 Vendor vendor name NO SIGNAL NAME CONTENTS 61 62 63 64 65 66 ...

Page 84: ...5 LED6_INFO LED6 Status 46 LED7_INFO LED7 Status 47 LED8_INFO LED8 Status 48 LED9_INFO LED9 Status 49 LED10_INFO LED10 Status 50 LED11_INFO LED11 Status 51 LED12_INFO LED12 Status 52 LED13_INFO LED13 Status 53 LED14_INFO LED14 Status 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 NO SIGNAL NAME CONTENTS 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 ...

Page 85: ...h 185 LD5_PHYHEALTH LD5 phycal Health 186 LD6_PHYHEALTH LD6 phycal Health 187 LD7_PHYHEALTH LD7 phycal Health 188 LD8_PHYHEALTH LD8 phycal Health 189 LD9_PHYHEALTH LD9 phycal Health 190 LD10_PHYHEALTH LD10 phycal Health 191 192 193 194 195 196 197 198 199 200 IFU_MODE IFU_MODE 201 IDE1_MODE IDE1_MODE 202 IDE2_MODE IDE2_MODE 203 IDE3_MODE IDE3_MODE 204 IDE4_MODE IDE4_MODE 205 IDE5_MODE IDE5_MODE 20...

Page 86: ... 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 NO SIGNAL NAME CONTENTS 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 RY1_STAT RY1 status 402 RY2_STAT RY...

Page 87: ...467 468 469 470 471 472 473 474 475 476 477 478 479 480 481 482 483 484 485 486 487 488 489 490 NO SIGNAL NAME CONTENTS 491 492 493 494 495 496 497 498 499 500 501 IED1_REC1_ST IED1_REC1_ST 502 IED2_REC1_ST IED2_REC1_ST 503 IED3_REC1_ST IED3_REC1_ST 504 IED4_REC1_ST IED4_REC1_ST 505 IED5_REC1_ST IED5_REC1_ST 506 IED6_REC1_ST IED6_REC1_ST 507 IED7_REC1_ST IED7_REC1_ST 508 IED8_REC1_ST IED8_REC1_ST ...

Page 88: ...Active SG 606 LD6_ACTSG LD6 Active SG 607 LD7_ACTSG LD7 Active SG 608 LD8_ACTSG LD8 Active SG 609 LD9_ACTSG LD9 Active SG 610 LD10_ACTSG LD10 Active SG 611 612 613 614 615 616 617 618 619 620 621 622 623 624 625 626 627 628 629 630 NO SIGNAL NAME CONTENTS 631 632 633 634 635 636 637 638 639 640 641 642 643 644 645 646 647 648 649 650 651 652 653 654 655 656 657 658 659 660 661 662 663 664 665 666 ...

Page 89: ...43 744 745 746 747 748 749 750 751 752 753 754 755 756 757 758 759 760 761 762 763 764 765 766 767 768 769 770 NO SIGNAL NAME CONTENTS 771 772 773 774 775 776 777 778 779 780 781 782 783 784 785 786 787 788 789 790 791 792 793 794 795 796 797 798 799 800 801 802 803 804 805 806 807 808 809 810 811 812 813 814 815 816 817 818 819 820 821 822 823 824 825 826 827 828 829 830 831 832 833 834 835 836 8...

Page 90: ...83 884 885 886 887 888 889 890 891 892 893 894 895 896 897 898 899 900 901 902 903 904 905 906 907 908 909 910 NO SIGNAL NAME CONTENTS 911 912 913 914 915 916 917 918 919 920 921 922 923 924 925 926 927 928 929 930 931 932 933 934 935 936 937 938 939 940 941 942 943 944 945 946 947 948 949 950 951 952 953 954 955 956 957 958 959 960 961 962 963 964 965 966 967 968 969 970 971 972 973 974 975 976 9...

Page 91: ...input 56 int 1057 GOOSE_IN_58S Goose input 57 int 1058 GOOSE_IN_59S Goose input 58 int 1059 GOOSE_IN_60S Goose input 59 int 1060 GOOSE_IN_61S Goose input 60 int 1061 GOOSE_IN_62S Goose input 61 int 1062 GOOSE_IN_63S Goose input 62 int 1063 GOOSE_IN_64S Goose input 63 int 1064 GOOSE_IN_65S Goose input 64 int 1065 GOOSE_IN_66S Goose input 65 int 1066 GOOSE_IN_67S Goose input 66 int 1067 GOOSE_IN_68S...

Page 92: ...UNTER_12 COUNTER 12 1212 COUNTER_13 COUNTER 13 1213 COUNTER_14 COUNTER 14 1214 COUNTER_15 COUNTER 15 1215 COUNTER_16 COUNTER 16 1216 COUNTER_17 COUNTER 17 1217 COUNTER_18 COUNTER 18 1218 COUNTER_19 COUNTER 19 1219 COUNTER_20 COUNTER 20 1220 COUNTER_21 COUNTER 21 1221 COUNTER_22 COUNTER 22 1222 COUNTER_23 COUNTER 23 1223 COUNTER_24 COUNTER 24 1224 COUNTER_25 COUNTER 25 1225 COUNTER_26 COUNTER 26 12...

Page 93: ...297 1298 1299 1300 FIX_CNT_1 FIX_CNT_1 1301 FIX_CNT_2 FIX_CNT_2 1302 FIX_CNT_3 FIX_CNT_3 1303 FIX_CNT_4 FIX_CNT_4 1304 FIX_CNT_5 FIX_CNT_5 1305 FIX_CNT_6 FIX_CNT_6 1306 FIX_CNT_7 FIX_CNT_7 1307 FIX_CNT_8 FIX_CNT_8 1308 FIX_CNT_9 FIX_CNT_9 1309 FIX_CNT_10 FIX_CNT_10 1310 FIX_CNT_11 FIX_CNT_11 1311 FIX_CNT_12 FIX_CNT_12 1312 FIX_CNT_13 FIX_CNT_13 1313 FIX_CNT_14 FIX_CNT_14 1314 FIX_CNT_15 FIX_CNT_15...

Page 94: ...43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 LEDRST_ORCAT 61 62 63 64 65 66 67 68 69 70 NO SIGNAL NAME CONTENTS 71 72 73 74 75 76 77 78 79 80 LEDRST_ORIDENT 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 LEDRST_TEST 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 LEDRST_CTLMDL 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137...

Page 95: ...83 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 LEDRST_SBOTIMEOUT 201 202 203 204 205 206 207 208 209 210 NO SIGNAL NAME CONTENTS 211 212 213 214 215 216 217 218 219 220 LEDRST_SBOCLASS 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268...

Page 96: ...26 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 NO SIGNAL NAME CONTENTS 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 CHGMOD_CHK 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 41...

Page 97: ...69 470 471 472 473 474 475 476 477 478 479 480 CHGMOD_ORIDENT 481 482 483 484 485 486 487 488 489 490 NO SIGNAL NAME CONTENTS 491 492 493 494 495 496 497 498 499 500 CHGMOD_TEST 501 502 503 504 505 506 507 508 509 510 511 512 513 514 515 516 517 518 519 520 CHGMOD_CTLMDL 521 522 523 524 525 526 527 528 529 530 531 532 533 534 535 536 537 538 539 540 CHGMOD_ST_ORCAT 541 542 543 544 545 546 547 548 ...

Page 98: ...601 602 603 604 605 606 607 608 609 610 611 612 613 614 615 616 617 618 619 620 CHGMOD_SBOCLASS 621 622 623 624 625 626 627 628 629 630 NO SIGNAL NAME CONTENTS 631 632 633 634 635 636 637 638 639 640 641 642 643 644 645 646 647 648 649 650 651 652 653 654 655 656 657 658 659 660 661 662 663 664 665 666 667 668 669 670 671 672 673 674 675 676 677 678 679 680 681 682 683 684 685 686 687 688 689 690 ...

Page 99: ...43 744 745 746 747 748 749 750 751 752 753 754 755 756 757 758 759 760 761 762 763 764 765 766 767 768 769 770 NO SIGNAL NAME CONTENTS 771 772 773 774 775 776 777 778 779 780 781 782 783 784 785 786 787 788 789 790 791 792 793 794 795 796 797 798 799 800 801 802 803 804 805 806 807 808 809 810 811 812 813 814 815 816 817 818 819 820 821 822 823 824 825 826 827 828 829 830 831 832 833 834 835 836 8...

Page 100: ...83 884 885 886 887 888 889 890 891 892 893 894 895 896 897 898 899 900 901 902 903 904 905 906 907 908 909 910 NO SIGNAL NAME CONTENTS 911 912 913 914 915 916 917 918 919 920 921 922 923 924 925 926 927 928 929 930 931 932 933 934 935 936 937 938 939 940 941 942 943 944 945 946 947 948 949 950 951 952 953 954 955 956 957 958 959 960 961 962 963 964 965 966 967 968 969 970 971 972 973 974 975 976 9...

Page 101: ... 1035 1036 1037 1038 1039 1040 BO_CNT_CTVAL 1041 1042 1043 1044 1045 1046 1047 1048 1049 1050 NO SIGNAL NAME CONTENTS 1051 1052 1053 1054 1055 1056 1057 1058 1059 1060 BO_CNT_ORCAT 1061 1062 1063 1064 1065 1066 1067 1068 1069 1070 1071 1072 1073 1074 1075 1076 1077 1078 1079 1080 BO_CNT_ORIDENT 1081 1082 1083 1084 1085 1086 1087 1088 1089 1090 1091 1092 1093 1094 1095 1096 1097 1098 1099 1100 BO_C...

Page 102: ...RIDENT 1161 1162 1163 1164 1165 1166 1167 1168 1169 1170 1171 1172 1173 1174 1175 1176 1177 1178 1179 1180 BO_CNT_SELCTED 1181 1182 1183 1184 1185 1186 1187 1188 1189 1190 NO SIGNAL NAME CONTENTS 1191 1192 1193 1194 1195 1196 1197 1198 1199 1200 BO_CNT_SBOTIMEOUT 1201 1202 1203 1204 1205 1206 1207 1208 1209 1210 1211 1212 1213 1214 1215 1216 1217 1218 1219 1220 BO_CNT_SBOCLASS 1221 1222 1223 1224 ...

Page 103: ... 102 6 F 2 S 0 8 7 7 ...

Page 104: ... 103 6 F 2 S 0 8 7 7 Appendix D Setting Sheet 1 Relay Unit Identification 2 Default setting ...

Page 105: ... 104 6 F 2 S 0 8 7 7 Setting Sheets 1 Relay Unit Identification Date Type Model Serial Number dc supply voltage Password Active setting group ...

Page 106: ...o Norm 26 BISW 25 Norm Inv ditto Norm 27 BISW 26 Norm Inv ditto Norm 28 BISW 27 Norm Inv ditto Norm 29 BISW 28 Norm Inv ditto Norm 30 BISW 29 Norm Inv ditto Norm 31 BISW 30 Norm Inv ditto Norm 32 BISW 31 Norm Inv ditto Norm 33 BISW 32 Norm Inv ditto Norm 34 BISW 33 Norm Inv ditto Norm 35 BISW 34 Norm Inv ditto Norm 36 BISW 35 Norm Inv ditto Norm 37 BISW 36 Norm Inv ditto Norm 38 BISW 37 Norm Inv d...

Page 107: ...8 In 2 0 3071 0 99 In 3 0 3071 0 100 In 4 0 3071 0 101 LED6_G Logic OR AND Configurable LEDs OR 102 Reset Inst Latch default LAN1 error Inst 103 In 1 0 3071 7 104 In 2 0 3071 0 105 In 3 0 3071 0 106 In 4 0 3071 0 107 LED6_R Logic OR AND Configurable LEDs OR 108 Reset Inst Latch default LAN1 error Inst 109 In 1 0 3071 7 110 In 2 0 3071 0 111 In 3 0 3071 0 112 In 4 0 3071 0 113 LED7_G Logic OR AND C...

Page 108: ...n 1 0 3071 0 164 In 2 0 3071 0 165 In 3 0 3071 0 166 In 4 0 3071 0 167 LED11_R Logic OR AND Configurable LEDs OR 168 Reset Inst Latch default Database errror Inst 169 In 1 0 3071 0 170 In 2 0 3071 0 171 In 3 0 3071 0 172 In 4 0 3071 0 173 LED12_G Logic OR AND Configurable LEDs OR 174 Reset Inst Latch Inst 175 In 1 0 3071 0 176 In 2 0 3071 0 177 In 3 0 3071 0 178 In 4 0 3071 0 179 LED12_R Logic OR ...

Page 109: ...0 240 In 6 0 3071 0 241 Logic OR AND OR 242 BOTD Off On Off 243 In 1 0 3071 1799 244 In 2 0 3071 2583 245 In 3 0 3071 0 246 In 4 0 3071 0 247 In 5 0 3071 0 248 In 6 0 3071 0 249 Logic OR AND OR 250 BOTD Off On Off 251 In 1 0 3071 1800 252 In 2 0 3071 2584 253 In 3 0 3071 0 254 In 4 0 3071 0 255 In 5 0 3071 0 256 In 6 0 3071 0 257 Logic OR AND OR 258 BOTD Off On Off 259 In 1 0 3071 1801 260 In 2 0 ...

Page 110: ...dress 192 315 GW1 2 0 255 Gateway Address 168 316 GW1 3 0 255 Gateway Address 19 317 GW1 4 0 255 Gateway Address 1 318 IP2 1 0 255 IP Address 192 319 IP2 2 0 255 IP Address 168 320 IP2 3 0 255 IP Address 19 321 IP2 4 0 255 IP Address 173 322 SM2 1 128 255 Subnet Mask 255 323 SM2 2 0 255 Subnet Mask 255 324 SM2 3 0 255 Subnet Mask 255 325 SM2 4 0 255 Subnet Mask 0 326 GW2 1 0 255 Gateway Address 19...

Page 111: ...On Server connect check Off 379 TSCCOMF 0 60 s Server connect check time 60 380 BITRN 0 128 Number of bi trigger on off events 100 381 EV1 0 3071 Event record signal 1 Refer to the E_record sheet 382 EV2 0 3071 Event record signal 2 ditto 383 EV3 0 3071 Event record signal 3 ditto 384 EV4 0 3071 Event record signal 4 ditto 385 EV5 0 3071 Event record signal 5 ditto 386 EV6 0 3071 Event record sign...

Page 112: ...gnal 73 ditto 454 EV74 0 3071 Event record signal 74 ditto 455 EV75 0 3071 Event record signal 75 ditto 456 EV76 0 3071 Event record signal 76 ditto 457 EV77 0 3071 Event record signal 77 ditto 458 EV78 0 3071 Event record signal 78 ditto 459 EV79 0 3071 Event record signal 79 ditto 460 EV80 0 3071 Event record signal 80 ditto 461 EV81 0 3071 Event record signal 81 ditto 462 EV82 0 3071 Event reco...

Page 113: ...ame20 Specified by user Event name 20 ditto 529 Event name21 Specified by user Event name 21 ditto 530 Event name22 Specified by user Event name 22 ditto 531 Event name23 Specified by user Event name 23 ditto 532 Event name24 Specified by user Event name 24 ditto 533 Event name25 Specified by user Event name 25 ditto 534 Event name26 Specified by user Event name 26 ditto 535 Event name27 Specified...

Page 114: ...fied by user Event name 91 ditto 600 Event name92 Specified by user Event name 92 ditto 601 Event name93 Specified by user Event name 93 ditto 602 Event name94 Specified by user Event name 94 ditto 603 Event name95 Specified by user Event name 95 ditto 604 Event name96 Specified by user Event name 96 ditto 605 Event name97 Specified by user Event name 97 ditto 606 Event name98 Specified by user Ev...

Page 115: ... 0 256 0 665 LD6 ARC1 I INF 0 256 0 666 LD7 ARC1 I INF 0 256 0 667 LD8 ARC1 I INF 0 256 0 668 LD9 ARC1 I INF 0 256 0 669 LD10 ARC1 I INF 0 256 0 670 LD1 ARC1 R INF 0 256 ARC1 Ready Information number LD1 0 671 LD2 ARC1 R INF 0 256 0 672 LD3 ARC1 R INF 0 256 0 673 LD4 ARC1 R INF 0 256 0 674 LD5 ARC1 R INF 0 256 0 675 LD6 ARC1 R INF 0 256 0 676 LD7 ARC1 R INF 0 256 0 677 LD8 ARC1 R INF 0 256 0 678 L...

Page 116: ...30 0 3071 ditto 1261 LD1 Offline On Off 31 EV31 0 3071 ditto 1262 LD2 Offline On Off 32 EV32 0 3071 ditto 1263 LD3 Offline On Off 33 EV33 0 3071 ditto 1264 LD4 Offline On Off 34 EV34 0 3071 ditto 1265 LD5 Offline On Off 35 EV35 0 3071 ditto 1266 LD6 Offline On Off 36 EV36 0 3071 ditto 1267 LD7 Offline On Off 37 EV37 0 3071 ditto 1268 LD8 Offline On Off 38 EV38 0 3071 ditto 1269 LD9 Offline On Off ...

Page 117: ... On Off 90 EV90 0 3071 ditto 0 On Off 91 EV91 0 3071 ditto 0 On Off 92 EV92 0 3071 ditto 0 On Off 93 EV93 0 3071 ditto 0 On Off 94 EV94 0 3071 ditto 0 On Off 95 EV95 0 3071 ditto 0 On Off 96 EV96 0 3071 ditto 0 On Off 97 EV97 0 3071 ditto 0 On Off 98 EV98 0 3071 ditto 0 On Off 99 EV99 0 3071 ditto 0 On Off 100 EV100 0 3071 ditto 0 On Off 101 EV101 0 3071 ditto On 102 EV102 0 3071 ditto On 103 EV10...

Page 118: ... 117 6 F 2 S 0 8 7 7 Appendix E Return Repair Form ...

Page 119: ... cho Fuchu shi Tokyo Japan For Power Systems Protection Control Department Quality Assurance Section Type G1IF4 Model Sub No Example Type G1IF4 Model 101A Sub No 10 L0 Product No Serial No Date 1 Reason for returning the relay mal function does not operate investigation others 2 Describe the details of the incident 3 Date incident occurred Day Month Year Example 10 July 2007 ...

Page 120: ... 119 6 F 2 S 0 8 7 7 4 Give any comments about the G1IF4 including the documents Customer Name Company Name Address Telephone No Facsimile No Signature ...

Page 121: ... 120 6 F 2 S 0 8 7 7 ...

Page 122: ... 121 6 F 2 S 0 8 7 7 Appendix F Technical Data ...

Page 123: ...850 SNTP Data transfer rate 100 Mbit sec Connector RJ45 TX SC FX Communication ports for protection relay Protocol IEC60870 5 103 Data transfer rate 19 200bit sec Physical medium RS485 communication Weight Approx 5 kg Temperature IEC60068 2 1 2 Operation guaranteed 10 C to 55 C Storage Transit 25 C to 70 C Dielectric IEC60255 4 2 kV at 50 or 60 Hz for 1 minute between all circuits and the case and...

Page 124: ... 123 6 F 2 S 0 8 7 7 Electrostatic discharge test IEC60255 22 2 class III 8 kV 10 Fast transient disturbance test IEC60255 22 4 class III 2 kV 10 ...

Page 125: ... 124 6 F 2 S 0 8 7 7 ...

Page 126: ... 125 6 F 2 S 0 8 7 7 Appendix G Ordering ...

Page 127: ... Ordering Interface Unit Type Interface unit G1IF4 Model 39BIs 12BOs 101 DC power supply rating 110 125Vdc 220 250Vdc 1 5 Communications RS485 x2 100BASE TX x1 100BASE FX x1 L Miscellaneous Simplex power supply 0 G1IF4 0 A ...

Page 128: ...minal Block Modified Appendix A DIOV1 2 0 Apr 27 2009 2 2 3 2 2 3 4 2 3 5 4 2 3 3 4 2 3 5 4 2 4 4 2 5 3 4 5 4 6 2 4 6 3 4 7 3 4 7 4 5 5 Appendices Modified the description Modified the description Modified the description Modified the description Modified the description Modified the description Modified the description Modified Appendix A and G 2 1 Oct 2 2017 Republished under spin off company ...

Page 129: ......