2.2
Installing the Module/Removing the Module
Unified Controller nv series Ethernet Module (EN655) Instruction Manual
11
2.2 Installing the Module/Removing the Module
EN655 is one slot type module. It is fixed to the base with both upper/lower lock levers and
mounting screws. Turn power OFF before installing and removing modules.
Procedure for installing
(1) Turn off the power of EN655 module and external power supplied to I/O modules.
(2) Check the mounting position of EN655.
Table 2-1 Locations where EN655 can be installed
(○ : Install OK, x: Install NG, - : NO SLOT)
Base-Unit
SLOT No.
S0 S1 S2 S3 S4 S5 S6 S7 S8
BU648E
×
○
○
○
○
○
○
○
○
BU643D
×
○
○
○
―
―
―
―
―
BU668
×
○
○
○
○
○
○
○
○
BU666
○
○
○
○
○
○
―
―
―
BU664
○
○
○
○
―
―
―
―
―
NOTE
1.
Total
electricity consumption
of modules installed in the same base must not exceed
the maximum output power rating.
For the electricity consumption of each module, refer to
" Unified Controller nv series
Controller Unit Instruction Manual (6F8C1220). Chapter 2.6 Power Supply Calculation”
2.
Install the module as close as possible to the CPU module (S0).
Summary of Contents for EN655
Page 1: ...Unified Controller nv series type1 light Ethernet Module EN655 Instruction Manual 6F8C1566 ...
Page 14: ... 6F8C1566 xii ...
Page 53: ...39 Chapter 5 Troubleshooting This chapter describes troubleshooting for the EN655 module ...
Page 62: ...Chapter 5 Troubleshooting 6F8C1566 48 ...
Page 92: ...Appendix A Specifications 6F8C1566 78 ...
Page 93: ...79 Appendix B Outside Dimensions ...
Page 95: ...81 Appendix C Related Products ...
Page 102: ...Appendix D Reference Calculation Table 6F8C1566 88 ...
Page 104: ...1566 2 1906 ...