Chapter 4 Settings
6F8C1686
60
4.4.1
Input/output data area batch access
1) Function
This is to write output data from the area (WRITE_DT) provided for the controller in the polling output data
area and bit strobe output data area of the DN611. If the data is for polling, specify a data size in the range
of 1 to 128 words; if it is for bit strobe, the data size is fixed at 4 words.
Input data is also copied from the polling/bit strobe input data area of the DN611B into the area (READ_DT)
provided by the controller. Specify a data size in the range of 1 to 128 words.
2) Diagrammatic representation (Function block)
DN_SLAVERW
REQ
DONE
CH
ERR
UNIT
STATUS
SLOT
READ_DT
N_RPOL
N_WPOL
WRITE_DT
Input Argument
Output Argument
REQ
BOOL type
Execution enabled
DONE
BOOL type
Completed
CH
WORD type
Channel No.
ERR
BOOL type
Error
UNIT
WORD type
Unit No.
STATUS
WORD type
Station status
SLOT
WORD type
Slot No.
READ_DT Data structural
Input data from
N_RPOL
UINT type
No. of polling input
words
type
slave device
N_WPOL
UINT type
No. of polling output
words
WRITE_DT Data structural
type
Output data to slave
device
Summary of Contents for DeviceNet nv Series
Page 30: ...Chapter 1 DN611B Introduction 6F8C1686 14 ...
Page 149: ...13 3 133 B Appendix B Outside Dimension ...
Page 159: ...1686 2 2201 ...