3.5 Connecting the DeviceNet transmission cable
Unified Controller nv Series DeviceNet Module DN611B Instruction Manual
27
3.5.2
Connecting DeviceNet cable to connector
1
Preparation of the DeviceNet cable
The cable end of the DeviceNet cable to be connected to the network connector of DN611B must be open type
(2 power lines, 2 signal lines, and 1 drain become to be in connector free circumstance). Or purchase a cable
that has been treated as an open type.
Cable sheath color
Description
Black
Network power line (V-)
Blue
Signal line (CAN_L)
-
Shield / Drain
White
Signal line (CAN_H)
Red
Network power line (V+)
5 to 7 mm
Approx. 30 mm
Figure 3-2 DeviceNet cable termination
2
Connect the DeviceNet cable to the network side connector
This section describes the network-side connector on the right side in Figure 3-1. Loosen the cable fixing
screws in advance as shown in Figure 3-3. Insert the cable into the connector with attention on the color of the
cable insulation and the marking color on the network-side connector. Tighten the cable fixing screw to fix each
cable.
Figure 3-3 Cable connection to network side connector
Color display
Black
Blue
White
Red
Cable fixing screw
Shield