Chapter 6 Troubleshooting
6F8C1686
100
Table 6-5 Comparison of Module Status Code O: Supported, X: Not supported
Code
DN611A Event
DN611B
Remarks
0
Normal status
O
1
Transmission not enabled
O
2
No data flow in the transmission line
O
3
Communication error
O
4
Scan list disagrees with the actual slave
composition.
O
5
Network error
O
6
Network power error detected.
O
9
Busoff is detected.
O
10
A duplicated node address is detected.
O
Table 6-6 Comparison of Node Status Detail O: Supported, X: Not supported
Code
Event
DN611B
Remarks
70
Detects an error in duplicate node address check.
O
72
Cannot communicate with slave devices.
O
73
Vendor ID, product type, and product code of a
slave device differ from those on the DN611B scan
list.
O
75
No slave device exists on the network. No slave
device is registered on the scan list.
O
76
DN611B has detected communication timeout due
to no response from slave devices.
O
77
Slave device transmission size differs from that on
the DN611B scan list.
O
78
DN611B unable to start transmission to slave
devices.
O
79
DN611B unable to send to slave devices.
O
80
DN611B's communication port is in idle mode.
O
81
DN611B's communication port is in fault mode.
O
82
Send/receive data fragment error
O
83
Slave device initialization refused.
O
84
Slave device initialization not completed.
O
85
DN611B receive buffer overflow
O
91
DN611B busoff
O
92
DN611B network power error
O
Summary of Contents for DeviceNet nv Series