Chapter 6 Troubleshooting
6F8C1686
122
2) Communication with slave devices interrupted
If the node status shows an error code, remove the cause of the trouble, referring to 6.1.3 RAS Information
Table 6-25 Slave Device Communication Check Items (2)
Description of Check
Check controller power
Check network cable connections (wrong wiring, breaks).
DN611B
Check the node address settings (for duplicate node
addresses).
Check the network communication rate settings (same
communication rate).
Check the local node parameter settings and the scan
list.
Check the slave devices for normal operation, referring
to the manual for the slave devices.
Check network cable connections (wrong wiring, breaks).
Slave device
Check the node address settings (for duplicate node
addresses).
Check the network communication rate settings (same
communication rate).
Check setting items specific to the slave devices.
Check the terminators at both ends of trunk cables (121
Ohms).
Check the maximum network length specified. Refer to
1.3.2 Trunk line/drop line and maximum cable length.
Check the drop cable length (6 m or less).
Network
Check the total extension of drop cables. Refer to 1.3.2
Trunk line/drop line and maximum cable length.
Check the network power supply method and power
capacity. Refer to 3.6.1 Network power supply method
and 3.6.3 Network power unit.
Check the grounding of the network cables. Refer to 3.6.4
Network grounding.