6.1 RAS
Unified Controller nv Series DeviceNet Module DN611B Instruction Manual
113
Table 6-18 Event Trace Items(1/2)
Event
Code
Detail
Information 1 (H)
Detail
Information 2 (H)
Detail
Information 3 (H)
Detail
Information 4 (H)
Description
0001H
Down code
1: Memory check
2: TRAP
3: WDT
Module down
0002H
01:Power ON
Station Status
Type of DN
02:Soft Reset
Station Status
module start.
03:Controller HALT
0003H
Before mode change
After mode change
Station change
0100H
Request ID
Request code
Completion status
Control port
0111H
Station status
Reset request
0112H
Type
00: Local station
setting
01: Port No. error
02: Node address
different
03: Polling mode
04: Scan time
05: Skip
06: Transmission
counter
Parameter
request
01: Slave setting
01: Number error
02: Port No. error
03: Node address
error
04: Same as local
station node address
specified
05: Data length error
0113H
Type
01: Unused BITON
Request mode
Present
station
status
Control request
02: Identical request
03: Permission bit ON
(invalid
in
STBY
mode)
04: STBY + RUN
05: RUN in run mode
06: Task start error
07: STBY in STBY
mode
08: Composition data
end
Parameter setting flag
Completion status
0118H
Request code (18H)
Completion status
Time setting
0407H
Error code
Duplicate node
address error
Summary of Contents for DeviceNet nv Series