106
H7 ASD Operation Manual
Jump Frequency #2 Bandwidth
Program
⇒
Special Control Parameters
⇒
Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency #2
(
Direct Access Number — F273
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Jump Frequency #3
Program
⇒
Special Control Parameters
⇒
Jump Frequencies
Same as Jump Frequency #1 (
) and is used when multiple frequencies are
to be jumped (see the plus-or-minus value setting at
). When multiple
jump frequencies overlap, the system will recognize the lowest and the highest
frequencies as one jump range.
Direct Access Number — F274
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (
)
Units — Hz
Jump Frequency #3 Bandwidth
Program
⇒
Special Control Parameters
⇒
Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency #3
(
Direct Access Number — F275
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Jump Frequency Processing
Program
⇒
Special Control Parameters
⇒
Jump Frequencies
⇒
Jump
Frequency Processing
This parameter determines if the output frequency of the ASD or the PID
feedback signal will be used as a reference for determining the Jump
Frequency range.
See
for further information on the Jump Frequency settings.
Settings:
Process Amount (use PID feedback)
Output Frequency
Direct Access Number — F276
Parameter Type — Selection List
Factory Default — Process Amount
Changeable During Run — Yes