Appendix F
H7 ASD Operation Manual
Appendix F
Link Reactor Information
Selection of a link reactor (DCL) is often application specific. This document will provide guidelines for
selecting link reactors for the H7 series of drives.
The 600 Volt series drives above 15 HP allow for the reactor to be mounted internal to the drive. All other
H7 drives require that the DCL be mounted externally.
When selecting and mounting an external DCL, the air flow around the reactor, the thermal capability of
the reactor, the allowable voltage loss, and the amount of harmonic reduction required will be
considerations.
Table 17
. DCL Selection Table.
Model Number
VT130H7U
DCL Part
Number
DCL Inductance
(mH)
DCL
(Amps)
2080
36350
0.40
30.0
2110
36351
0.30
38.0
2160
36376
0.20
57.0
2220
36353
0.20
76.0
2270
36355
0.10
114
4110
36358
1.30
20.0
4160
36359
0.90
29.0
4220
36360
0.70
39.0
4270
36361
0.50
50.0
4330
36363
0.40
75.0
4400
36364
0.30
88.0
4500
36365
0.20
114
4600
36365
0.20
114
4750A
36366
0.20
141
410KA
42769
0.14
205
6060
36356
2.50
11.0
6120
36359
0.90
29.0
6160
36359
0.90
29.0
6220
36360
0.70
39.0
6270
36362
0.50
55.0
6330
36361
0.50
50.0
6400
36363
0.40
75.0
6500
36363
0.40
75.0
6600
36364
0.30
88.0